7.9 Other functions
7.9.2 Servo end check function
Use the servo end check function to detect the positioning operation completion by the servo status in-
position signal. When the servo status in-position signal turns ON after operation completion (within the range
of servo end check determination time) the 20SSC-H detects that the positioning operation has ended.
When the in-position signal does not turn ON within the specified servo end determination time, an external
error occurs, stopping the operation.
→ For the parameters, control data and monitor data, refer to Chapter 11
1. Set as follows when using the servo end check.
Servo end evaluation time
When the set value of the servo end evaluation time is outside the setting range, the set value is handled as
follows:
• Zero or smaller settings are handled as "1ms."
• 5001 or larger settings are handled as "5000ms."
2. Applicable positioning operations
BFM Number
Description
X-axis Y-axis
Servo end check
enabled/disabled
Operation
parameter 2
BFM #14002
b0
BFM #14202
b0
Enables or disables the servo end check function.
1(ON): Enable
0(OFF): Disable
Servo end evaluation time BFM #14032 BFM #14232
This parameter sets the evaluation time for the servo end check.
Setting range: 1 to 5000 ms
In-position Servo status
BFM #64
b12
BFM #164
b12
This bit is set while droop pulses are within a range of "In-
position."
In-position range BFM #15010 BFM #15210
Set the range to output a positioning completion signal in units of
command pulses.
Setting range: 0 to 65535 PLS
• Operations applicable to the servo end check • Operations inapplicable to the servo end check
- JOG operation
- 1-speed positioning operation
- Interrupt 1-speed constant quantity feed
- 2-speed positioning operation
- Interrupt 2-speed constant quantity feed
- Interrupt stop
- Variable speed operation
- Multi-speed operation
- Linear interpolation
- Linear interpolation (interrupt stop)
- Circular interpolation
- Mechanical zero return
- Reciprocal movement instruction
(Ver.1.10 or later)
- During continuous multi-speed operation
- During continuous pass operation of
interpolation operation
- Manual pulse generator operation