11 Buffer Memory (Parameters & Monitored Data)
11.4 Control Data
238
FX3U-20SSC-H Positioning Block User's Manual
11.4.3 Target address 2 [BFM #505, #504, BFM #605, #604]
This data item sets a target position or travel distance for the positioning operation distance as the target
address 2.
*1. Refer to the section shown below for details on the user units.
Refer to Section 7.10
Note
The positioning operation differs as follows depending on the procedure to specify the absolute address or
relative address.
- With absolute address: travels from the current position to the target position.
The rotation direction depends on whether target address 2 is larger or smaller than the current address.
- With relative address: moves by the specified travel distance from the current position. The rotation
direction depends on the target address sign (+/-).
The units of the value are user-specified and include the position data magnification.
11.4.4 Operation speed 2 [BFM #507, #506, BFM #607, #606]
This data item sets the operation speed 2 for positioning operations.
*1. Refer to the section shown below for details on the user units.
Refer to Section 7.10
Note
Set the operation speed 2 lower than the maximum speed.
If the operation speed 2 exceeds the maximum speed, the 20SSC-H operates at the maximum speed.
Use the override function or operation speed change function when changing the operation speed during
operation.
For details of the override operation, refer to Subsection 7.6.1
For details on the operation speed change function, refer to Subsection 7.6.2
11.4.5 Override setting [BFM #508, BFM #608]
This data item sets an override value for the override function.
For details on the override function, refer to Subsection 7.6.1
11.4.6 Torque output setting value [BFM #510, BFM #610]
This data item sets an output torque for the torque limit function.
For details on the torque limit function, refer to Subsection 7.9.3
BFM Number
Description Default
X-axis Y-axis
BFM
#505,#504
BFM
#605,#604
Setting range: -2,147,483,648 to 2,147,483,647 [User unit]
*1
Set the value within -2,147,483,648 to 2,147,483,647 PLS in the converted pulse data
K0
BFM Number
Description Default
X-axis Y-axis
BFM
#507,#506
BFM
#607,#606
Setting range: 1 to 2,147,483,647 [User unit]
*1
Set the value within 1 to 50,000,000 Hz in converted pulse data.
K1
BFM Number
Description Default
X-axis Y-axis
BFM #508 BFM #608 Setting range: 1 to 30000 (× 0.1%) K1000
BFM Number
Description Default
X-axis Y-axis
BFM #510 BFM #610 Setting range: 0 to 10000 (× 0.1%) K0