HVAC Drive H300 11
Issue Number: 3
2 Product information
2.1 Drive firmware version
This product is supplied with the latest firmware version. If this drive is to be connected to an existing system or machine, all drive firmware versions
should be verified to confirm the same functionality as drives of the same model already present. This may also apply to drives returned from an
Nidec Industrial Automation Service Centre or Repair Centre. If there is any doubt please contact the supplier of the product.
The firmware version of the drive can be checked by looking at Pr 00.050 {11.029}.
2.2 AC drive for fans, pumps and compressors
The H300 is a high performance open loop AC drive specifically designed for use in building automation / Commercial HVAC/R applications. Figure 2-
1 below indicates the key product features including built in connectivity to building automation systems. Each drive is equipped with three identical
option slots for I/O and communications expansion.
Figure 2-1 Features
The H300 drive can be used as a stand alone motor controller or integrated into a building automation system using analog and digital I/O or serial
communications. The base drive incorporates a EIA-485 serial communications port that is selectable between Modbus RTU, BACnet MSTP or
Metasys N2 Open.
DeviceNet, CANopen, Ethernet and PROFIBUS connectivity is achieved with the addition of plug-in option modules
Key features:
• Universal high performance drive for induction and sensorless permanent magnet motors.
• Onboard IEC 61131-3 programmable automation
• Dual integrated form C relay outputs
• NV Media Card for parameter copying and data storage
• EIA-485 serial communications interface
• Single channel Safe Torque Off (STO) input
Fire mode
Fire Mode is a configurable override function that is used to alter the operation of the drive based upon external inputs, typically a discrete digital input
from a Building Management Fire Protection system.
Building Automation System
Fieldbus:
Automation:
I/O Expansion
SI-DeviceNet
SI-CANopen
SI-Ethernet
SI-PROFINET V2
SI-I/O
Onboard:
EIA 485
Modbus RTU
BACnet MSTP
Metasys N2 Open
Automation:
MCi200
MCi210
SI-Applications Plus