Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization
NV Media Card
Operation
Building
Automation
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
182 HVAC Drive H300
Issue Number: 3
Analog input objects
Analog output objects
To control an analog output via BACnet the source parameter for the output must be set to a read/write parameter on menu 18. (Pr 18.011 to
Pr 18.030 are acceptable).
Device object properties
The following list describes the Device Object properties supported on the BAN interface with H300.
Table 10-19 Device Object properties
Object ID (AIn) Object name Description Present value access mode
1 Drive analog input 1 Analog input 1 on drive (Pr 07.001)RO
2 Drive analog input 2 Analog input 2 on drive (Pr 07.002)RO
3 Drive analog input 3 Analog input 3 on drive (Pr 07.003)RO
4 Module x analog input 1
The first available analog input on a
Solutions Module.
RO
↓↓ ↓ ↓
n Module x analog input n
The n
th
available analog input on a
Solutions Module
RO
Object ID (AOn) Object name Description Present value access mode
1 Drive analog output 1 Analog output 1 on drive C
2 Drive analog output 2 Analog output 2 on drive C
3 Module x analog output 1
The first available analog output on a
Solutions Module
C
↓↓ ↓ ↓
n Module x analog output 1
The first available analog output on a
Solutions Module
C
Device Object Property
APDU-timeout
Application software version
Database revision
Firmware revision
Local date
Local time
Max-APDU-length-accepted
Model name
Number of APDU retries
Object identifier
Object-list
Object-name
Object-type
Protocol object types supported
Protocol-version
Segmentation-supported
System-status
Vendor-identifier
Vendor-name