HVAC Drive H300 305
Issue Number: 3
Power Data Power system configuration data error
220
The Power Data trip indicates that there is an error in the configuration data stored in the power system.
Recommended actions:
• Hardware fault – Contact the supplier of the drive
Power Down Save Power down save error
37
The Power Down Save trip indicates that an error has been detected in the power down save parameters saved in non-
volatile memory.
Recommended actions:
• Perform a 1001 save in Pr mm.000 to ensure that the trip doesn’t occur the next time the drive is powered up.
PSU Internal power supply fault
5
The PSU trip indicates that one or more internal power supply rails are outside limits or overloaded.
*For a parallel power-module system the rectifier number will be zero as it is not possible to determine which rectifier has
detected the fault.
Recommended actions:
• Remove any option modules and perform a reset
• Remove encoder connection and perform a reset
• Hardware fault within the drive – return the drive to the supplier
PSU 24V 24V internal power supply overload
9
The total user load of the drive and option modules has exceeded the internal 24 V power supply limit. The user load
consists of the drive digital outputs and main encoder supply.
Recommended actions:
• Reduce the load and reset
• Provide an external 24 V power supply on control terminal 2
• Remove all option modules
Trip Diagnosis
Source xx y zz Description
Control
system
00 0 02 There is no data table to be uploaded to the control board
Control
system
00 0 03
The power system data table is bigger than the space available in
the control pod to store it.
Control
system
00 0 04 The size of the table given in the table is incorrect.
Control
system
00 0 05 Table CRC error.
Control
system
00 0 06
The version number of the generator software that produced the
table is too low. i.e. a table from a newer generator is required that
includes features that have been added to the table that may not
be present.
Power
system
Power
module
number
000
The power data table used internally by the power module has an
error. (For a multi-power module drive this indicates any error with
the code tables in the power system).
Power
system
Power
module
number
001
The power data table that is uploaded to the control system on
power up has an error.
Power
system
Power
module
number
002
The power data table used internally by the power module does
not match the hardware identification of the power module.
Source xx y Description
Control
system
00 0 Internal power supply overload
Power
system
Power
module
number
Rectifier
number*
Rectifier internal power supply overload