Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization
NV Media Card
Operation
Building
Automation
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
74 HVAC Drive H300
Issue Number: 3
3.13.8 Size 7 to 11 auxiliary (capacitor bank) fan replacement
Figure 3-64 Size 7 to 11 auxiliary (capacitor bank) fan replacement
Size 7 to 11 auxiliary fan removal procedure
1) Disconnect the fan wiring connector shown
2) Slide fan housing in the direction shown using tongue shown in enlarged diagram of fan
3) Withdraw fan housing from the drive
After fan has been replaced, reverse the above steps to refit.
Table 3-29 Size 7 to 11 Auxiliary (capactitor bank) fan part numbers
Drive model Auxiliary (capacitor bank fan part number
Size 7 3251-0041
Size 8 3251-2249
Size 9, 10 and 11 (575V and 690V) 3251-0042
Size 11 (400V) 3251-1202