186 HVAC Drive H300
Issue Number: 3
Within each region, there may be up to 256 "points" which are a selected group of drive parameters that can be accessed. The points available in the
drive are detailed in the sections below.
10.5.2 Analog Inputs
Analog input points are numeric parameters (real) that are read-only.
The drive only supports integer parameters with implied decimal point, any such parameter returned by a Metasys query will be in IEEE floating point
(not the internal representation in the drive). An analog input cannot be written to but can be overridden. Note that analog inputs, being read-only,
cannot be updated on the drive. In this case, overriding an analog input will only change what the Metasys network sees as the value of that point.
Point 24 to 28 have limited functionality, they do not support attribute 1 and 8 to 12.
Table 10-25 Analog input points
NOTE
Point Parameter Description Access Latch on trip
0 04.001 Motor output current magnitude RO Yes
1 04.020 Motor output torque % full load RO No
2 05.001 Drive output frequency RO Yes
3 05.004 Motor Speed RO No
4 05.003 Drive output power RO Yes
5 10.040 Drive status word RO No
6 10.020 Last drive trip RO No
7 06.023 Time to next filter change RO No
8 06.025 Energy meter (MWh) RO No
9 06.026 Energy meter (kWh) RO No
10 14.020 Sum of all reference inputs to PID 1 RO No
11 14.021 Sum of all feedback inputs to PID 1 RO No
12 14.001 The output from PID 1 RO No
13 14.050 Sum of all reference inputs to PID 2 RO No
14 14.051 Sum of all feedback inputs to PID 2 RO No
15 14.031 The output from PID 2 RO No
16 07.001 Analog input 1 on drive RO Yes
17 07.002 Analog input 2 on drive RO Yes
18 Reserved Reserved
19 UP 29.010 User Selectable Parameter 1 as BAN Object RO No
20 UP 29.011 User Selectable Parameter 2 as BAN Object RO No
21 UP 29.012 User Selectable Parameter 3 as BAN Object RO No
22 UP 29.013 User Selectable Parameter 4 as BAN Object RO No
23 UP 29.014 User Selectable Parameter 5 as BAN Object RO No
24 UP 29.015 User Selectable Parameter 6 as BAN Object RO No
25 UP 29.016 User Selectable Parameter 7 as BAN Object RO No
26 UP 29.017 User Selectable Parameter 8 as BAN Object RO No
27 UP 29.018 User Selectable Parameter 9 as BAN Object RO No
28 UP 29.019 User Selectable Parameter 10 as BAN Object RO No