Table 12-5 Losses @ 40°C (104° F) ambient with high IP insert installed
Model
Normal Duty
Drive losses (W) taking into consideration any current derating for the given conditions
2 kHz 3 kHz 4 kHz 6 kHz 8 kHz 12 kHz 16 kHz
200 V
03200066 88 93 95 99 104 113 122
03200080 95 100 102 107 113 122 133
03200110 117 123 126 133 140 158 157
03200127 122 128 124 122 118 98 84
04200180 138 145 151 151 146 142 146
04200250 204 215 205 194 189 187 199
05200300 188 194 201 212 222 240 262
400 V
03400034 76 80 84 94 103 123 137
03400045 84 88 92 102 105 110 134
03400062 80 84 85 89 92 109 134
03400077 108 114 117 122 135 172 203
03400104 112 118 134 155 173 221 267
03400123 112 118 134 155 173 221 267
04400185 100 105 114 132 153 197 207
04400240 96 101 111 131 152 197 207
05400300 118 118 119 124 132 152 183
575 V
05500039
32 42 52 71 92 133 173
05500061
70 85 100 130 159 219 278
05500100
123 144 165 210 252 338 424