EasyManua.ls Logo

Nidec H300 - Menu 29: Building Automation Network Setup

Nidec H300
322 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running
the motor
Optimization
NV Media Card
Operation
Building
Automation
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
258 HVAC Drive H300
Issue Number: 3
11.20 Menu 29: Building Automation Network Setup
Parameter Range Default Type
29.001 BAN Protocol Selection
Modbus RTU (0),
BACnet MSTP (1),
Metasys N2 Open (2)
Modbus RTU (0) RW Txt US
29.003 MS/TP Maximum Master MAC Address 0 to 127 127 RW Num US
29.004 Device Object Identifier 0 to 4194302 1 RW Num US
29.005 Communications Lost Detection Time-Out Period 5 to 60000 s 5 s RW Num US
29.006 Communications Lost Action 0 to 2 0 RW Num PT US
29.010 User Selectable Parameter 1 0.000 to 41.999 0.000 RW Num PT US
29.011 User Selectable Parameter 2 0.000 to 41.999 0.000 RW Num PT US
29.012 User Selectable Parameter 3 0.000 to 41.999 0.000 RW Num PT US
29.013 User Selectable Parameter 4 0.000 to 41.999 0.000 RW Num PT US
29.014 User Selectable Parameter 5 0.000 to 41.999 0.000 RW Num PT US
29.015 User Selectable Parameter 6 0.000 to 41.999 0.000 RW Num PT US
29.016 User Selectable Parameter 7 0.000 to 41.999 0.000 RW Num PT US
29.017 User Selectable Parameter 8 0.000 to 41.999 0.000 RW Num PT US
29.018 User Selectable Parameter 9 0.000 to 41.999 0.000 RW Num PT US
29.019 User Selectable Parameter 10 0.000 to 41.999 0.000 RW Num PT US
29.020 CRC Errors 0 to 65535 RW Num ND NC PT
29.021 Token Interval 0.000 to 65.535 s RO Num ND NC PT
29.022 Received Message Counter 0 to 65535 RO Num ND NC PT
29.023 Derivative Status -1 to 3 RO Num ND NC PT
29.024 Software Version 0 to 99999999 RO Num ND NC PT
RW Read / Write RO Read Only Bit Bit Parameter Txt Text String Date Date Parameter Time Time Parameter
Chr Character Parameter Bin Binary Parameter IP IP Address Mac Mac Address Ver Version Number SMP Slot, menu, parameter
Num Number Parameter DE Destination ND No Default Value RA Rating dependant NC Non- copyable PT Protected
FI Filtered US User Save PS Power-Down Save