6 Basic parameters
6.1 Menu 0: Basic parameters
Parameter
Range Default
Type
OL RFC-A RFC-S OL RFC-A RFC-S
00.001
Motor Rpm {05.004} ±180000 rpm
RO Num ND NC PT FI
Speed Feedback {03.002}
VM_SPEED rpm RO Num ND NC PT FI
00.002 Output Frequency {05.001}
VM_SPEED_FREQ_
REF Hz
±2000.0 Hz
RO Num ND NC PT FI
00.003 Current Magnitude {04.001}
0.000 to VM_DRIVE_CURRENT_
UNIPOLAR A
RO Bit ND NC PT FI
00.004 Output Power (05.003) VM_POWER kW
RO Num ND NC PT FI
00.005 Software Version {11.029} 00.00.00.00 to 99.99.99.99
RO Num ND NC PT
00.010
Minimum Reference
Clamp
{01.007} VM_NEGATIVE_REF_CLAMP1 Hz / rpm 0.0 Hz / rpm RW Num US
00.011
Maximum Reference
Clamp
{01.006}
VM_POSITIVE_REF_CLAMP1
Hz / rpm
50 Hz default:
50.0 Hz
60 Hz default:
60.0 Hz
50 Hz
default:
1500.0
rpm
60 Hz
default:
1800.0
rpm
3000.0
rpm
RW Num US
00.012 Acceleration Rate 1 {02.011}
0.0 to
VM_ACCEL_RATE
s to Pr 01.006
0.000 to
VM_ACCEL_RATE
s to Pr 01.006
20.0 s
to Pr 01.006
20.000 s
to Pr 01.006
RW Num US
00.013 Deceleration Rate 1 {02.021}
0.0 to
VM_ACCEL_RATE
s from Pr 01.006
0.000 to
VM_ACCEL_RATE
s from Pr 01.006
20.0 s
from Pr 01.006
20.000 s
from Pr 01.006
RW Num US
00.014
Open-loop Control Mode {05.014}
Ur S (0), Ur (1),
Fixed (2),
Ur Auto (3),
Ur I (4),
Square (5),
Current 1P (6)
Ur I (4) RW Txt US
Speed Controller
Proportional Gain Kp1
{03.010} 0.0000 to 200.0000 s/rad 0.0300 s/rad RW Num US
00.015
Dynamic V to F Select {05.013}
Off (0) or
On (1)
On (1) RW Bit US
Speed Controller Integral
Feedback Gain Ki 1
{03.011}
0.00 to 655.35
s
2
/rad
0.10 s
2
/rad
RW Num US
00.016
Low Frequency Voltage
Boost
{05.015} 0.0 to 25.0 % 1.0 % RW Num US
Speed Controller
Differential Feedback
Gain Kd1
{03.012} 0.00000 to 0.65535 1/rad 0.00000 1/rad RW Num US
00.017 Number Of Motor Poles {05.011} Automatic (0) to 480 Poles (240) Automatic (0) 8 Poles (4) RW Num US
00.018 Rated Voltage {05.009} 0 to VM_AC_VOLTAGE_SET V
200V drive: 230V
50Hz default 400V drive: 400V
60Hz default 400V drive: 460V
575V drive: 575V
690V drive: 690V
RW Num RA US
00.019 Rated Speed {05.008} 0 to 33000 rpm 0.00 to 33000.00 rpm
50 Hz default -
1500 rpm
60 Hz default-
1800 rpm
50 Hz
default -
1450.00
rpm
60 Hz
default-
1750.00
rpm
3000.00
rpm
RW Num US
00.020 Rated Current {05.007} 0.000 to VM_RATED_CURRENT A
Maximum rated current
(Pr 11.060) A
RW Num RA US
00.021
Rated Frequency {05.006} 0.0 to 550.0 Hz
50Hz default: 50.0
60Hz default: 60.0
RW Num US
Volts per 1000 rpm {05.033}
0 to 10000 V
/ 1000 rpm
98 V /
1000 rpm
RW Num US
00.022
Maximum Switching
Frequency
{05.018}
2 kHz (0), 3 kHz (1), 4 kHz (2), 6 kHz (3), 8 kHz (4),
12 kHz (5), 16 kHz (6)
3 kHz (1) RW Txt RA US
00.023 Catch A Spinning Motor {06.009}
Disable (0), Enable (1),
Fwd Only (2), Rev Only (3)
Disable (0) RW Txt US
00.024 Auto-tune {05.012} 0 to 2 0 to 2 0, 1, 2, 6 0 RW Num NC
Menu 0 is used to bring together various commonly used parameters for basic easy set up of the drive. All the parameters in Menu 0 appear in other
menus in the drive (denoted by {…}). Menu 22 can be used to configure the parameters in Menu 0.