HVAC Drive H300 165
Issue Number: 3
When this parameter is set to OFF (0) the integrator operates normally.
Setting this parameter to On (1) will cause the integrator value to be
held. Setting this parameter does not prevent the integrator from being
reset to zero if the PID controller is disabled.
If PID is used to control the motor output via Menu 1 and sleep mode is
enabled, then the drive will automatically stop the motor when the output
drops below the sleep/wake threshold. The feedback may then fall
causing the output and hence the feedback to rise again. Setting
Pr 14.028 and Pr 14.029 to non zero values results in the value in
Pr 14.028 being added to the PID reference for a length of time defined
in Pr 14.029 when the drive attempts to enter sleep mode.. This will
reduce the frequency of the transitions into sleep mode. Pr 14.030
indicates when the boost system is enabled.
14.015 PID 1 output scaling
14.045 PID 2 output scaling
RW Uni US
Ú
0.000 to 4.000
Ö
1.000
14.016 PID 1 output destination parameter
14.046 PID 2 output destination parameter
RW Uni DE PT US
Ú
Pr 0.000 to Pr 50.099
Ö
Pr 0.000
14.017 PID 1 integrator hold
14.047 PID 2 integrator hold
RW Bit NC US
Ú
OFF (0) or On (1)
Ö
OFF (0)
14.018 PID 1 symmetrical limit enable
14.048 PID 2 symmetrical limit enable
RW Bit US
Ú
OFF (0) or On (1)
Ö
OFF (0)
14.019 PID 1 main reference
14.049 PID 2 main reference
RO Bi NC PT US
Ú
±100.00 %
Ö
14.020 PID 1 reference
14.050 PID 2 reference
RO Bi NC PT US
Ú
±100.00 %
Ö
14.021 PID 1 feedback
14.051 PID 2 feedback
RO Bi NC PT US
Ú
±100.00 %
Ö
14.022 PID 1 error
14.052 PID 2 error
RO Bi NC PT US
Ú
±100.00 %
Ö
14.023 PID 1 reference scaling
14.053 PID 2 reference scaling
RW Uni US
Ú
0.000 to 4.000
Ö
1.000
14.024 PID 1 feedback scaling
14.054 PID 2 feedback scaling
RW Uni US
Ú
0.000 to 4.000
Ö
1.000
14.025 PID 1 digital reference
14.055 PID 2 digital reference
RW Bi NC
Ú
±100.00 %
Ö
0.00
14.026 PID 1 digital feedback
14.055 PID 2 digital feedback
RW Bi NC
Ú
±100.00 %
Ö
0.00
14.027 PID 1 optional enable source parameter 2
RW Uni PT US
Ú
0.00 to 50.99
Ö
0.00
14.028 PID 1 pre-sleep boost level
RW Uni US
Ú
0.00 to 100.00 %
Ö
0.00
14.029 Maximum boost time
RW Uni US
Ú
0.0 to 250.0 s
Ö
0.0
14.030 PID 1 pre-sleep boost level enable
RO Bit NC PT
Ú
OFF (0) or On (1)
Ö
14.038 PID 2 enable
RW Uni US
Ú
0 to 2
Ö
0
Parameter
value
PID enable state
0
PID 2 disabled; output is zero and integrator reset to
zero
1 PID 2 enabled
2 PID 2 enable state follows PID 1 enable state