HVAC Drive H300 291
Issue Number: 3
Card No Data NV Media Card data not found
183
The Card No Data trip indicates that an attempt has been made to access non-existent file or block on a NV Media Card.
No data is transferred.
Recommended actions:
• Ensure data block number is correct
Card Option NV Media Card trip; option modules installed are different between source drive and destination drive
180
The Card Option trip indicates that parameter data or default difference data is being transferred from a NV Media Card to
the drive, but the option module categories are different between source and destination drives. This trip does not stop the
data transfer, but is a warning that the data for the option modules that are different will be set to the default values and not
the values from the card. This trip also applies if a compare is attempted between the data block and the drive.
Recommended actions:
• Ensure the correct option modules are installed.
• Ensure the option modules are in the same option module slot as the parameter set stored.
• Press the red reset button to acknowledge that the parameters for one or more of the option modules installed will be at
their default values
• This trip can be suppressed by setting Pr mm.000 to 9666 and resetting the drive.
Card Product NV Media Card data blocks are not compatible with the drive derivative
175
If Drive Derivative (11.028) or Product Type (11.063) are different between the source and target drives then this trip is
initiated either at power-up or when the card is accessed. It will have one of the following sub-trip numbers:
Recommended actions:
• Use a different NV Media Card
• This trip can be suppressed by setting Pr mm.000 to 9666 and resetting the drive
Card Rating NV Media Card Trip; The voltage and / or current rating of the source and destination drives are different
186
The Card Rating trip indicates that parameter data is being transferred from a NV Media Card to the drive, but the current
and / or voltage ratings are different between source and destination drives. This trip also applies if a compare (using
Pr mm.000 set to 8yyy) is attempted between the data block on a NV Media Card and the drive. The Card Rating trip does
not stop the data transfer but is a warning that rating specific parameters with the RA attribute may not be transferred to the
destination drive.
Recommended actions:
• Reset the drive to clear the trip
• Ensure that the drive rating dependent parameters have transferred correctly
• This trip can be suppressed by setting Pr mm.000 to 9666 and resetting the drive.
Card Read Only NV Media Card has the Read Only bit set
181
The Card Read Only trip indicates that an attempt has been made to modify a read-only NV Media Card or a read-only data
block. A NV Media Card is read-only if the read-only flag has been set.
Recommended actions:
• Clear the read only flag by setting Pr mm.000 to 9777 and reset the drive. This will clear the read-only flag for all data
blocks in the NV Media Card
• This trip can be suppressed by setting Pr mm.000 to 9666 and resetting the drive.
Card Slot NV Media Card Trip; Option module application program transfer has failed
174
The Card Slot trip is initiated, if the transfer of an option module application program to or from an application module failed
because the option module does not respond correctly. If this happens this trip is produced with the sub-trip indicating the
option module slot number.
Recommended actions:
• Ensure the source / destination option module is installed on the correct slot
Trip Diagnosis
Sub-trip Reason
1
If Drive Derivative (11.028) is different between the source and target drives, this trip is initiated either at
power-up or when the SD Card is accessed. Data is still transferred, since this is a warning trip; the trip
can be suppressed by entering code 9666 in parameter xx.000, and resetting the drive (this applies the
warning suppression flag to the card).
2
If Product Type (11.063) is different between the source and target drives or if corruption is detected in
the parameter file, this trip is initiated either at power-up or when the SD Card is accessed. This trip can
be reset but no data are transferred in either direction between the drive and the card.
3
A Unidrive SP parameter value was found that has no equivalent parameter on the destination drive.
Data is still transferred, since this is a warning trip; the trip can be suppressed by entering code 9666 in
Pr xx.000, and resetting the drive (this applies the warning suppression flag to the card).