146 HVAC Drive H300
Issue Number: 3
7.4 Quick start commissioning / start-up using HVAC Drive Connect (V02.00.05 onwards)
HVAC Drive Connect is a Windows™ based software commissioning/start-up tool for H300 drives. HVAC Drive Connect can be used for
commissioning / start-up and monitoring, drive parameters can be uploaded, downloaded and compared and simple or custom menu listings can be
created. Drive menus can be displayed in standard list format or as live block diagrams. HVAC Drive Connect is able to communicate with a single
drive or a network. HVAC Drive Connect can be downloaded from www.controltechniques.com (file size approximately 100 MB). A KI-485 Adaptor
and suitable USB to EIA-485 isolated converter is required for connection to HVAC Drive Connect. A suitable isolated converter is available from
Control Techniques:
CT USB Comms Cable (CT part number 4500-0096).
HVAC Drive Connect system requirements
Windows 8, Windows 7 SP1, Windows Vista SP2, Windows XP SP3
Minimum of 1280 x 1024 screen resolution with 256 colours
Microsoft.Net Frameworks 4.0 (this is provided in the downloaded file)
Note that you must have administrator rights to install HVAC Drive Connect
Any previous copy of HVAC Drive Connect should be uninstalled before proceeding with the installation (existing projects will not be lost). Included
within the software is the Parameter Reference Guide for H300.
7.4.1 Power-up the drive
1. Start HVAC Drive Connect, and on the ‘Project Management’ screen select 'Scan serial RTU network' or 'Scan all connected drives’. Select the
discovered drive.