HVAC Drive H300 301
Issue Number: 3
OHt Power Power stage over temperature
22
This trip indicates that a power stage over-temperature has been detected. The sub-trip "xxyzz" indicates which thermistor
is indicating the over-temperature. The thermsitor numbering is different for a single module type drive (i.e. no parallel
board fitted) and a multi-module type drive (i.e. parallel board fitted with one or more power modules) as shown below:
Single module type drive:
Multi-module type system:
Note that the power module that has caused the trip cannot be identified except for the braking IGBT temperature
measurement
Recommended actions:
• Check enclosure / drive fans are still functioning correctly
• Force the heatsink fans to run at maximum speed
• Check enclosure ventilation paths
• Check enclosure door filters
• Increase ventilation
• Reduce the drive switching frequency
• Reduce duty cycle
• Decrease acceleration / deceleration rates
• Reduce motor load
• Check the derating tables and confirm the drive is correctly sized for the application.
• Use a drive with larger current / power rating
OI ac Instantaneous output over current detected
3
The instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX. This trip cannot be reset until 10 s
after the trip was initiated.
Recommended actions:
• Acceleration/deceleration rate is too short
• If seen during auto-tune reduce the voltage boost
• Check for short circuit on the output cabling
• Check integrity of the motor insulation using an insulation tester
• Check feedback device wiring
• Check feedback device mechanical coupling
• Check feedback signals are free from noise
• Is motor cable length within limits for the frame size
• Reduce the values in the speed loop gain parameters - (Pr 03.010, 03.011, 03.012) or (Pr 03.013, 03.014, 03.015)
• Has the phase angle autotune been completed? (RFC-S mode only)
• Reduce the values in current loop gain parameters (RFC-A, RFC-S modes only)
Trip Diagnosis
Source xx y zz Description
Power system 01 0 zz Thermistor location defined by zz in the power board
Power system 01
Rectifier number
zz Thermistor location defined by zz in the rectifier
Source xx y zz Description
Power system power module number 0 01 U phase power device
Power system power module number 0 02 V phase power device
Power system power module number 0 03 W phase power device
Power system power module number 0 04 Rectifier
Power system power module number 0 05 General power system
Power system power module number 0 00 Braking IGBT
Source xx y zz Description
Control
system
00 0
00
Instantaneous over-current trip when the measured a.c. current
exceeds VM_DRIVE_CURRENT[MAX].
Power
system
Power
module
number
0