192 HVAC Drive H300
Issue Number: 3
Table 10-45
10.5.7 List of Metasys Commands Supported
Table 10-46 List of Metasys commands supported
Table 10-47 List of Metasys commands NOT supported
Change of State Support
The H300 Metasys Protocol handler permits Change-of-State (COS) queries. This allows the network to poll a Metasys node (H300) to determine
which points have changed value since the last query. The response to such a poll is a list of those points that have changed, including the region
number, point number, status and current value. It is possible that the COS response contains multiple points that have changed. The report that a
point has changed state is only given once, future COS polls will go unanswered until the point actually changes state again. This is a great
convenience to the Metasys user in that the network doesn't have to continually poll a large number of points to detect a change; rather a list of these
points is sent to the H300 node and polling queries will result in just the specified points being checked for change. The results are culled into a single
response message. Best of all, if nothing happened since the last poll, there is no response (just a short acknowledgement).
Selecting Points for COS Polling
Analog Input, Binary Input, Analog Output and Binary Output Points all can be selected for COS polling. The user must set the COS_Enable bit
beforehand. For example, to place the "Drive Healthy" Pr 10.001 into the COS polling list, we just need to write to its configuration byte and set the
COS_Enable bit.
Table 10-48 Binary input- object configuration byte
Set COS Enable bit to place Binary Input, Point 2 (Drive Healthy) into the COS polling list.
Point Parameter Description
0 N/A Not implemented
Command
Synch Time Command Write Binary Output Command
Poll Without Ack Message Write Internal Parameter Command
Read Analog Input Command Override Analog Input Command
Read Binary Input Command Override Binary Input Command
Read Analog Output Command Override Analog Output Command
Read Binary Output Command Override Binary Output Command
Read Internal Parameter Command Override Internal Parameter Command
Write Analog Input Command Override Release Request
Write Binary Input Command Identify Device Type Command
Write Analog Output Command -
Command
Read Memory Command Read Binary Input Attributes Request
Warm Start Read Analog Output Attributes Request
Status Update Request Read Binary Output Attributes Request
Write Internal Parameter Command Upload Request
Write Analog Input Attributes Request Upload Record
Write Binary Input Attributes Request Upload Complete
Write Analog Output Attributes Request Download Request
Write Binary Output Attributes Request Download Record
Read Analog Input Attributes Request Download Complete
Description Not used Not used Not used Not used Alarm Enable Not used Normal State COS Enable
Bit76543210