296 HVAC Drive H300
Issue Number: 3
HF12 Data processing error: Main program stack overflow
The HF12 trip indicates that the main program stack over flow has occurred. The stack can be identified by the sub-trip
number. This trip indicates that the control PCB on the drive has failed.
Recommended actions:
Hardware fault – Contact the supplier of the drive
HF13 Data processing error: Firmware incompatible with hardware
The HF13 trip indicates that the drive firmware is not compatible with the hardware. This trip indicates that the control PCB
on the drive has failed. The sub-trip number gives the actual ID code of the control board hardware.
Recommended actions:
Re-program the drive with the latest version of the drive firmware
Hardware fault – Contact the supplier of the drive
HF14 Data processing error: CPU register bank error
The HF14 trip indicates that a CPU register bank error has occurred. This trip indicates that the control PCB on the drive
has failed.
Recommended actions:
Hardware fault – Contact the supplier of the drive
HF15 Data processing error: CPU divide error
The HF15 trip indicates that a CPU divide error has occurred. This trip indicates that the control PCB on the drive has
failed.
Recommended actions:
Hardware fault – Contact the supplier of the drive
HF16 Data processing error: RTOS error
The HF16 trip indicates that a RTOS error has occurred. This trip indicates that the control PCB on the drive has failed.
Recommended actions:
Hardware fault – Contact the supplier of the drive
HF17 Data processing error: Clock supplied to the control board is out of specification
The HF17 trip indicates that the clock supplied to the control board logic is out of specification. This trip indicates that the
control PCB on the drive has failed.
Recommended actions:
Hardware fault – Contact the supplier of the drive
HF18 Data processing error: Internal flash memory has failed
The HF18 trip indicates that the internal flash memory has failed when writing option module parameter data. The reason
for the trip can be identified by the sub-trip number.
Recommended actions:
Hardware fault - Contact the supplier of the drive.
HF19 Data processing error: CRC check on the firmware has failed
The HF19 trip indicates that the CRC check on the drive firmware has failed.
Recommended actions:
Re-program the drive
Hardware fault - Contact the supplier of the drive
Trip Diagnosis
Sub-trip Stack
1 Background tasks
2 Timed tasks
3 Main system interrupts
Sub-trip Reason
1 Option module initialization timed out
2 Programming error while writing menu in flash
3 Erase flash block containing setup menus failed
4 Erase flash block containing application menus failed
5 Incorrect setup menu CRC contained in flash
6 Incorrect application menu CRC contained in flash
7 Incorrect common application menu 18 CRC contained in flash
8 Incorrect common application menu 19 CRC contained in flash
9 Incorrect common application menu 20 CRC contained in flash