In modes 2 and 3, a current loop loss trip is generated if the current falls
below 3 mA.
In modes -4, -3, 2 and 3 the analog input level goes to 0.0 % if the input
current falls below 3 mA.
In modes -2 and -1 the analog input remains at the value it had in the
previous sample before the current fell below 3 mA.
Pr 00.028 sets the destination of analog input 2
Analog Input 2 Thermistor Type (00.029) selects the type of temperature
feedback device used with analog Input 2 when Analog Input 2 Mode
(00.027) is set-up for temperature feedback mode. When a temperature
feedback mode is selected, 5V is applied to the output via a 3.3K Ω
resistor to supply current through the temperature measuring device.
If any number other than 0 is programmed into this parameter, user
security is applied so that no parameters except Pr 00.031 can be
adjusted with the keypad. When this parameter is read via a keypad, it
appears as 0. For further details refer to section 5.9.3 User Security
Code on page 117.
This parameter controls access via the drive keypad as follows:
The keypad can adjust this parameter even when user security is set.
This parameter shows the number of the data block last transferred from
a SMARTCARD to the drive.
00.027 {07.011} Analog Input 2 Mode
RW Txt US
OL
Ú
4-20 mA Low (-4),
20-4 mA Low (-3),
4-20 mA Hold (-2),
20-4 mA Hold (-1),
0-20 mA (0),
20-0 mA (1),
4-20 mA Trip (2),
20-4 mA Trip (3),
4-20 mA (4),
20-4 mA (5), Volt (6),
Therm Short Cct (7),
Thermistor (8),
Therm No Trip (9)
Ö
Volt (6)
RFC-A
RFC-S
Pr Value Pr string Comments
-4 4-20 mA Low
4-20 mA low value on
current loss (1)
-3 20-4 mA Low
20-4 mA low value on
current loss (1)
-2 4-20 mA Hold
4-20 mA hold at level before
loss on current loss
-1 20-4 mA Hold
20-4 mA hold at level before
loss on current loss
0 0-20 mA
1 20-0 mA
2 4-20 mA Trip 4-20 mA trip on current loss
3 20-4 mA Trip 20-4 mA trip on current loss
4 4-20 mA
5 20-4 mA
6Volt
7 Therm Short Cct
Temperature Measurement
Input With Short Circuit
Detection
8Thermistor
Temperature Measurement
Without Short Circuit
Detection
9 Therm No Trip
Temperature Measurement
Input With No Trips
00.028 {07.014} Analog Input 2 Destination
RW Num DE PT US
OL
Ú
00.000 to 59.999
Ö
01.036RFC-A
RFC-S
00.029 {07.058}
Analog Input 2 Thermistor Type
RW Txt US
OL
Ú
DIN44082 (0)
KTY84 (1)
PT100 (2)
PT1000 (3)
PT2000 (4)
NI1000 (5)
Ö
DIN44082(0)
RFC-A
RFC-S
00.030 {11.030} User Security Code
RW Num ND NC PT US
OL
Ú
0 to 2147483647
Ö
0RFC-A
RFC-S
00.031 {11.044} User Security Status
RW Txt ND PT
OL
Ú
Menu 0 (0), All Menus (1),
Read-only Menu 0 (2),
Read-only (3),
Status Only (4),
No Access (5)
Ö
Menu 0 (0)
RFC-A
RFC-S
Security
level
Description
0
(Menu 0)
All writable parameters are available to be edited but
only parameters in Menu 0 are visible.
1
(All Menus)
All writable parameters are visible and available to be
edited.
2
(Read-only
Menu 0)
All parameters are read-only. Access is limited to Menu 0
parameters only.
3
(Read-only)
All parameters are read-only however all menus and
parameters are visible.
4
(Status Only)
The keypad remains in status mode and no parameters
can be viewed or edited.
5
(No Access)
The keypad remains in status mode and no parameters
can be viewed or edited. Drive parameters cannot be
accessed via a comms / fieldbus interface in the drive or
any option module.
00.032 {11.044} NV Media Card Data Previously Loaded
RO Num NC PT
OL
Ú
0 to 999
Ö
0RFC-A
RFC-S