276 HVAC Drive H300
Issue Number: 3
12.1.21 Protective ground cable ratings
Table 12-22 Protective ground cable ratings
12.1.22 Maximum motor cable lengths
Table 12-23 Maximum motor cable lengths (200 V drives)
Input phase
conductor size
Minimum ground conductor size
≤ 10 mm
2
Either 10 mm
2
or two conductors of the same cross-sectional area as the input phase conductor (an additional ground
connection is provided on sizes 3, 4 and 5 for this purpose).
> 10 mm
2
and ≤ 16 mm
2
The same cross-sectional area as the input phase conductor
> 16 mm
2
and ≤ 35 mm
2
16 mm
2
> 35 mm
2
Half of the cross-sectional area of the input phase conductor
200 V Nominal AC supply voltage
Model
Maximum permissible motor cable length for each of the following switching frequencies
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz
03200066 65 m (210 ft)
50 m (165 ft) 37 m (120 ft)
03200080 100 m (330 ft)
75 m (245 ft)03200110 130 m (425 ft)
100 m (330 ft)
03200127 200 m (660 ft) 150 m (490 ft)
04200180
200 m (660 ft) 150 m (490 ft) 100 m (330 ft) 75 m (245 ft) 50 m (165 ft) 37 m (120 ft)
04200250
05200300 200 m (660 ft) 150 m (490 ft) 100 m (330 ft) 75 m (245 ft) 50 m (165 ft) 37 m (120 ft)
06200500
200 m (660 ft) 150 m (490 ft) 100 m (330 ft) 75 m (245 ft) 50 m (165 ft) 37 m (120 ft)
06200580
07200750
250 m (820 ft) 187 m (614 ft) 125 m (410 ft) 93 m (305 ft) 62 m (203 ft) 46 m (151 ft)
07200940
07201170
08201490
250 m (820 ft) 187 m (614 ft) 125 m (410 ft) 93 m (305 ft) 62 m (203 ft) 46 m (151 ft)
08201800
09202160
250 m (820 ft) 187 m (614 ft) 125 m (410 ft) 93 m (305 ft) 62 m (203 ft) 46 m (151 ft)
09202660
10203250
250 m (820 ft) 187 m (614 ft) 125 m (410 ft) 93 m (305 ft) 62 m (203 ft) 46 m (151 ft)
10203600