Issue Number: 3
00.025 Analog Input 1 Mode {07.007}
4-20 mA Low (-4),
20-4 mA Low (-3), 4-20 mA Hold (-2),
20-4 mA Hold (-1), 0-20 mA (0),
20-0 mA (1),4-20 mA Trip (2),
20-4 mA Trip (3), 4-20 mA (4), 20-4 mA (5), Volt (6),
Therm Short Cct (7), Thermistor (8),
Therm No Trip (9)
4-20 mA (4) RW Txt US
00.026
Analog Input 1
Destination
{07.010} 0.000 to 59.999 01.036 RW Num DE PT US
00.027 Analog Input 2 Mode {07.011}
4-20 mA Low (-4), 20-4 mA Low (-3),
4-20 mA Hold (-2), 20-4 mA Hold (-1), 0-20 mA (0),
20-0 mA (1), 4-20 mA Trip (2),
20-4 mA Trip (3), 4-29 mA (4),
20-4 mA (5), Volt (6), Therm Short Cct (7),
Thermistor (8), Therm No Trip (9)
Volt (6) RW Txt US
00.028
Analog Input 2
Destination
{07.014} 00.000 to 59.999 01.037 RW Num DE PT US
00.029
Analog Input 2 Thermistor
Type
{07.058}
DIN44082 (0), KTY84 (1), PT100 (2), PT1000 (3),
PT2000 (4), NI1000 (5)
DIN44082 (0) RW Txt US
00.030 User Security Code {11.030} 0 to 2147483647 0 RW Num ND NC PT US
00.031 User Security Status {11.044}
Menu 0 (0), All Menus (1), Read-only Menu 0 (2),
Read-only (3), Status Only (4), No Access (5)
Menu 0 (0) RW Txt ND PT
00.032
NV Media Card Data
Previously Loaded
{11.036} 0 to 999 0 RO Num NC PT
00.033 Parameter Cloning {11.042} None (0), Read (1), Program (2), Auto (3), Boot (4) None (0) RW Txt NC US
00.034 Date {06.016} 00-00-00 to 31-12-99 RW Date ND NC PT
00.035 Time {06.017} 00:00:00 to 23:59:59 RW Time ND NC PT
00.036 Day Of Week {06.018}
Sunday (0), Monday (1), Tuesday (2), Wednesday (3),
Thursday (4), Friday (5), Saturday (6)
RO Txt ND NC PT
00.037 Date/Time Selector {06.019}
Set (0), Powered (1), Running (2), Acc Powered (3),
Local Keypad (4), Remote Keypad (5),
Slot 1 (6), Slot 2 (7), Slot 3 (8), Slot 4 (9)
Local Keypad (4) RW Txt US
00.038 Date Format {06.020} Std (0) or US (1) US (1) RW Txt US
00.040
RFC Low
Speed Mode
{05.064}
Injection (0),
Non-salient
(1),
Current (2),
Current No
Test (3)
Non-
salient
(1)
RW Txt US
00.041
Low Speed
Sensorless
Mode Current
{05.071}
0.0 to
1000.0 %
20.0 % RW Num RA US
00.042 No-load Lq {05.072}
0.000 to
500.000 mH
0.000
mH
RW Num RA US
00.043
Iq Test Current
for Inductance
Measurement
{05.075}
0to
200 %
100 % RW Num US
00.044
Phase Offset At
Iq Test Current
{05.077} ±90.0 ° 0.0 ° RW Num RA US
00.045
Lq At The
Defined Iq
Test Current
{05.078}
0.000 to
500.000 mH
0.000
mH
RW Num RA US
00.046
Id Test
Current for
Inductance Measurement
{05.082}
-100 to
0 %
-50 % RW Num US
00.047
Lq At The
DefinedIdTest
Current
{05.084}
0.000 to
500.000 mH
0.000
mH
RW Num RA US
00.048
Number Of Auto-reset
Attempts
{10.034} None (0), 1 (1), 2 (2), 3 (3), 4 (4), 5 (5), Infinite (6) 5 (5) RW Txt US
00.049 Auto-reset Delay {10.035} 0.0 to 600.0 s 5.0 s RW Num US
00.050 Trip 0 {10.020} 0 to 255 R O T x t N D N C P T P S
00.051 Trip 1 {10.021} 0 to 255 R O T x t N D N C P T P S
00.052 Trip 2 {10.022} 0 to 255 R O T x t N D N C P T P S
00.053 Trip 3 {10.023} 0 to 255 R O T x t N D N C P T P S
00.054 Trip 4 {10.024} 0 to 255 R O T x t N D N C P T P S
00.055 Trip 5 {10.025} 0 to 255 R O T x t N D N C P T P S
00.056 Trip 6 {10.026} 0 to 255 R O T x t N D N C P T P S
00.057 Trip 7 {10.027} 0 to 255 R O T x t N D N C P T P S
00.058 Trip 8 {10.028} 0 to 255 R O T x t N D N C P T P S
00.059 Trip 9 {10.029} 0 to 255 R O T x t N D N C P T P S
00.060 Trip 0 Date {10.041} 00-00-00 to 31-12-99 RO Date ND NC PT PS
00.061 Trip 0 Time {10.042} 00:00:00 to 23:59:59 RO Time ND NC PT PS
00.062 Trip 1 Date {10.043} 00-00-00 to 31-12-99 RO Date ND NC PT PS
Parameter
Range Default
Type
OL RFC-A RFC-S OL RFC-A RFC-S