Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization
NV Media Card
Operation
Building
Automation
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
HVAC Drive H300 263
Issue Number: 3
55 ° C ratings are available on request.
11404370
437 415 374 298 240
11404870
462 415 374 298 240
11405070
462 415 374 298 240
575 V
05500039
3.9
05500061
6.1
05500100
10
06500120
12
06500170
17 13.4
06500220
22 17.8 13.4
06500270
27 23.5 17.8 15
06500340
34 28.2 23.5 18 15
06500430
43.0 41.7 36.1 28 23.7 18 15
07500530
53 46.7 35.8 24.8 19
07500730
73 65 46.7 35.8 24.8 19
08500860
86 76.7 64.5 44.3 31.3
08501080
104 97.2 90.7 76.7 64.8 44.3 31.3
09501250
125 114 90 62 48
09501500
150 114 90 62 48
10502000
200 184 154 114 90 62 48
11502480
226 198
11502880
262 241 198
11503150
296 241 198
690 V
07600230
23 19
07600300
30 24.8 19
07600360
36 35.8 24.8 19
07600460
46 35.8 24.8 19
07600520
52 46.7 35.8 25 19
07600730
73 65 46.7 35.8 25 19
08600860
86 76.7 64.5 44.3 31.3
08601080
104 97.2 90.7 76.7 64.8 44.3 31.3
09601250
125 114 90 62 48
09601550
155 153 113 89 62 48
10601720
172 153 114 89 62 48
10601970
197 195 134 102 67 48
11602250
205 198
11602750
250 241 198
11603050
296 241 198
Model
Normal Duty
Maximum permissible continuous output current (A)
for the following switching frequencies
2
kHz
3
kHz
4
kHz
6
kHz
8
kHz
12
kHz
16
kHz