Chapter 6
6-16
Message Communications
01
16 Speed scale Speed data unit selection
can be set and read. The
speed data unit value is
calculated as follows:
Unit = 1 [r/min] x 1/2
a
a: Speed scale set value
Set a negative value as its
2's complement.
−15 to 15 (F1
to 0F hex)
00 Yes Yes Byte
17 Current scale Current data unit selection
can be set and read. The
current data unit value is
calculated as follows:
Unit = 0.1 [A] x 1/2
b
b: Current scale set
value
Set a negative value as its
2's complement.
−15 to 15 (F1
to 0F hex)
00 Yes Yes Byte
1A Power scale Power data unit selection
can be set and read. The
power data unit value is
calculated as follows:
Unit = 1 [W] x 1/2
c
c: Power scale set value
Set a negative value as its
2's complement.
−15 to 15 (F1
to 0F hex)
00 Yes Yes Byte
1B Voltage scale Voltage data unit selection
can be set and read. The
voltage data unit value is
calculated as follows:
Unit = 1 [V] x 1/2
d
d: Voltage scale set
value
Set a negative value as its
2's complement.
−15 to 15 (F1
to 0F hex)
00 Yes Yes Byte
1C Time scale Time data unit selection
can be set and read. The
time data unit value is cal-
culated as follows:
Unit = 1 [ms] x 1/2
e
e: Voltage scale set
value
Set a negative value as its
2's complement.
−15 to 15 (F1
to 0F hex)
00 Yes Yes Byte
1D Reference From
Net
(See note 1.)
00: Reference other than
DeviceNet (n004/b1-01)
01: Operating with
DeviceNet.
--- 00 Yes No Byte
64 Electric power Average power value (W) --- 0000
0000
Yes No Long
65 Electric power
time scale
Power value measure-
ment period (T) (reflected
when power is turned ON)
00: 10 minutes
01: 30 minutes
02: 60 minutes
00 to 02 00 Yes Yes Byte
6F Specific alarm Alarm code of the alarm or
minor fault detected in the
Inverter. For more details,
refer to 8-5 Inverter
Alarms.
--- 0000 Yes No Word
70 Specific error Fault code of the fault
detected in the Inverter.
For more details, refer to
8-4 Inverter Faults.
--- 00 Yes No Byte
Instance Attribute Name Content Setting range Default Read Write Size