Chapter 7
7-47
Configurator Settings
Note When the 3G3RV/3G3PV is used, all parameters can be set from the Configurator.
3G3FV
Parameter Group
Parameters that Cannot be Set on the Inverter Parameters Tab Page
(Use the Individual Parameters Tab Page)
Parameters that Cannot Be Set from the Configurator (Use the Digital Operator)
H4-07 04 23 Multi-function analog output 1 (terminal FM) signal level selection
H4-08 04 27 Multi-function analog output 2 (terminal AM) signal level selection
o1-05 05 04 LCD brightness
o2-04 05 08 Inverter capacity selection
Parameter group Details
All Parameters Initialize Mode Parameters A: Environment settings (A1-02 only)
Application Group B: Application
Tuning Parameters C: Tuning
Reference Parameters D: Reference
Motor Constant Parameters E: Motor constant
Option Parameter F: Option
Terminal Parameter H: Terminal function setting
Protection Parameter L: Protection function
Operator Parameter O: Operator
Enter Code Enter code
Monitor Speed reference, speed monitor, current moni-
tor, output voltage
Parameter
No.
Class 64 Details
Instance Attribute
C6-01 01 3D Carrier frequency upper limit
C6-02 01 3E Carrier frequency lower limit
C6-03 01 3F Carrier frequency proportional gain
Parameter No.
A: Environment settings All parameters except A1-02
B: Application b1-06, b1-07, b1-08, b2-08, b4-01, b4-02, b5-09, b5-10, b5-11, b5-12, b5-13,
and b5-14
C: Tuning C1-10, C1-11, C3-06, C4-03, C4-04, C4-05, C8-09, and C8-30
E: Motor constant E1-03, E2-10, E3-@@, E4-@@, and E5-@@
F: Option F2-@@, F3-@@, F4-@@, F7-@@, and F9-@@
L: Protection function L8-17 and L8-19
Parameter
No.
Class 64 Details
Instance Attribute