Chapter 10
10-10
Appendices
Note 1. “Produced” means output (Inverter to PLC), and “Consumed” means input (PLC to Inverter).
Note 2. Instance 02 is a Poll connection, Instance 03 is a Bit-strobe connection, and Instance 04 is
a COS or Cyclic connection.
Note 3. The following table shows the connection path for each Instance.
Produced Connection Path
02
03
04
Remote
I/O
(See
note 2.)
08 Consumed con-
nection size
Indicates the maximum
number of bytes for recep-
tion.
--- See note
3.
Ye s N o W o r d
09 Expected packet
rate
Indicates the length of the
internal processing time-
out when a communica-
tions request is received.
Incremented by 10-ms
units.
0 to 65,535
(ms)
0000
(0 ms)
Ye s Ye s W o r d
0C Watchdog time-
out action
Indicates the action for
internal processing time-
out related to communica-
tions.
00: Retain timeout status
(until reset or cleared).
--- 00 Yes No Byte
0D Produced con-
nection path
length
Indicates number of bytes
of data for produced con-
nection path.
--- See note
3.
Ye s N o W o r d
0E Produced con-
nection path
Indicates the data for
defining the application
object for sending this
object (instance).
* Has a function for
switching the DeviceNet
Communication Unit/
Card’s remote I/O oper-
ation.
--- See note
3.
Ye s N o A r r a y
0F Consumed con-
nection path
length
Indicates the number of
bytes of data for the con-
sumed connection path.
--- See note
3.
Ye s N o W o r d
10 Consumed con-
nection path
Indicates the data for
defining the application
object for receiving this
object (instance).
* Has a function for
switching the DeviceNet
Communication Unit/
Card's remote I/O oper-
ation.
--- See note
3.
Ye s N o A r r a y
Remote I/O function Connection
Size
Path
Length
Connection Path Remarks
46 hex: Basic remote I/O (input) 0004 0006 20 04 24 46 30 03 ---
47 hex: Standard remote I/O
(input)
0004 0006 20 04 24 47 30 03 Instance 02
default setting
96 hex: Special remote I/O (input) 0005 0006 20 04 24 96 30 03 ---
97 hex: Control I/O remote I/O
(input)
0008 0006 20 04 24 97 30 03 ---
Instance Attribute Name Content Setting range Default Read Write Size