Chapter 10
10-15
Appendices
ā Object Details
Instance Attribute Name Content Setting range Default Read Write Size
00 01 Object Software
Revision
Indicates class 29 soft-
ware revisions. The revi-
sion value is advanced
whenever there is a
change.
--- 0001 Yes No Word
01 03 Forward/Stop 00: Stop
01: Forward operation
00, 01 00 Yes Yes Byte
04 Reverse/Stop 00: Stop
01: Reverse operation
00, 01 00 Yes Yes Byte
05 Net Control
Local/remote
switch
(Set note 1.)
00: Operation set in n003/
b1-02.
01: Force DeviceNet oper-
ation (not valid with
3G3FV).
00, 01 00 Yes Yes Byte
06 State
Inverter status
(See note 1.)
00 hex: Vendor specific
01 hex: Startup
02 hex: Not ready
03 hex: Inverter ready
04 hex: Enabled
05 hex: Stopping
06 hex: Fault_Stop
07 hex: Faulted
--- 03 Yes No Byte
07 During forward
run
00: No Inverter output or
operating in reverse.
01: Forward operation or
DC braking
Turns ON even for DC
braking during reverse
operation.
-- 00 Yes No Byte
08 During reverse
run
00: No Inverter output or
operating in forward.
01: Operating in reverse
(reverse operation output
status)
Becomes ā00" with DC
braking.
-- 00 Yes No Byte
09 Inverter Ready 00: Preparing
Initial processing/ not
drive mode/ fault
01: Inverter ready
Inverter can receive run
command.
-- 00 Yes No Byte
0A Fault 00: Normal
01: Fault
-- 00 Yes No Byte
0B Alarm (minor
fault)
00: Normal
01: Alarm (minor fault)
-- 00 Yes No Byte
0C Fault Reset 00: Normal status
01: Fault reset
00, 01 00 Yes Yes Byte
0D Fault code Indicates the contents of
fault that occur. (See the
fault code list on the fol-
lowing page.)
--- 0000 Yes No Word
0F Control From
Net
Run signal input
status
(See note 2.)
00: Operating by a method
other than DeviceNet that
is set in n003/b1-02.
01: Operating by
DeviceNet.
--- 00 Yes No Byte
10 DeviceNet Fault
mode
(See note 3.)
00: Stop operation.
01: Continue operation.
02: Maker's specifications
3G3MV: 00,
01
3G3RV: ---
3G3FV: ---
3G3MV: 00
3G3RV: 02
3G3FV: 02
Ye s Ye s B y t e