Chapter 10
10-16
Appendices
Note 1. The following table shows the status of remote I/O output signals and operation indicated by
the content of Attribute 06 (State, i.e., Inverter status).
Note 2. The Net Control and Control From Net functions cannot be changed during running.
Note 3. A DeviceNet Fault mode can be set from communications in the 3G3MV only; it cannot be
changed from communications in the 3G3RV or 3G3FV. Set the fault mode in the Inverter’s
parameters.
Fault Codes
01 11 Force Fault/Trip
Communica-
tions external
fault input
00: Normal operation
01: Communications
external fault input
00, 01 00 Yes Yes Byte
12 Force Status
Communica-
tions external
fault input status
00: Normal status
01: Communications
external fault detected.
(Inverter stopped with fault
detection.)
--- 00 Yes No Byte
Setting Status Condition
00 hex Vendor specific A condition other than the ones
below.
01 hex Startup: Preparation not complete (setting con-
stants)
Inverter Ready signal is OFF.
02 hex Not ready: Stopped (preparation complete) Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
03 hex Inverter ready: Stopped (preparation complete) Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
04 hex Enabled: Operating During Run signal (control I/O) is
ON.
05 hex Stopping: Decelerating (Operating with both for-
ward and reverse references equal to 0.)
Ctrl. From Net is ON, During Forward
Run is OFF, During Reverse Run is
OFF, and During Run is ON.
06 hex Fault_Stop: Operating with fault detected Alarm signal is ON.
07 hex Faulted: Fault detected Fault signal is ON.
DeviceNet error code Operator display Meaning
0000 --- Inverter normal
2120 GF Ground fault
2130 SC Short circuit
2200 OL2 Inverter overload
2220 OL1 Motor overload
2221 OL3 Overtorque detection 1
2222 OL4 Overtorque detection 2
2300 OC Overcurrent
3130 PF Input phase loss
LF Output phase loss
3210 OV Main circuit overvoltage
3220 UV1 Undervoltage (main)
3222 UV3 Undervoltage (MC)
4200 OH Overheat
Instance Attribute Name Content Setting range Default Read Write Size