Chapter 10
10-78
Appendices
Note 1. Values in parentheses are for 400-V-class Inverters.
Note 2. The settings of E1-11 and E1-12 are ignored if set to 0.0.
Note 3. E1-13 will be the same value as E1-05 after autotuning.
Note 4. The setting range is 10% to 200% of the Inverter's rated output current. The values for a 200-
V-class 0.4-kW Inverter are given above.
E1-10 0309 03 09 Min. output frequency volt-
age
0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 9.0
(18.0)
(See
note 1.)
No
E1-11 030A 03 0A Mid. output frequency 2 0.0 to
120.0
0.1 Hz 0.0
(See
note 2.)
No
E1-12 030B 03 0B Mid. output frequency volt-
age 2
0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 0.0
(See
note 2.)
No
E1-13 030C 03 0C Base voltage 0.0 to
255.0
(0.0 to
510.0)
(See
note 1.)
0.1 V 0.0
(See
note 3.)
No
E2-01 030E 03 0E Motor rated current 0.32 to
6.40
(See
note 4.)
0.01 A De-
pends
on ca-
pacity.
No
E2-05 0312 03 12 Motor line-to-line resistance 0.000 o
65.000
0.001
De-
pends
on ca-
pacity.
No
Param-
eter
Register
No.
(Hex)
Class 64 (Hex) Name Setting
range
Setting
unit
Default
setting
Changes
during
opera-
tion
In-
stance
At-
tribute