Chapter 10
10-81
Appendices
L2-01 0485 04 85 Momentary power loss
detection
0 to 2 1 0 No
L2-02 0486 04 86 Momentary power loss ride-
thru time
0 to 2.0 0.1 s De-
pends
on ca-
pacity.
No
L2-03 0487 04 87 Min. baseblock time 0.1 to
5.0
0.1 s De-
pends
on ca-
pacity.
No
L2-04 0488 04 88 Voltage recovery time 0.0 to
5.0
0.1 s De-
pends
on ca-
pacity.
No
L2-05 0489 04 89 Undervoltage detection
level
150 to
210
(150 to
420)
(See
note.)
1 V 190
(380)
(See
note.)
No
L3-01 048F 04 8F Stall prevention selection
during accel
0 to 2 1 1 No
L3-02 0490 04 90 Stall prevention level during
accel
0 to 200 1% 120 No
L3-04 0492 04 92 Stall prevention selection
during decel
0 to 2 1 1 No
L3-05 0493 04 93 Stall prevention selection
during running
0 to 2 1 1 No
L3-06 0494 04 94 Stall prevention level during
running
30 to
200
1% 120 No
L4-01 0499 04 99 Speed agreement detec-
tion level
0.0 to
400.0
0.1 Hz 0.0 No
L4-02 049A 04 9A Speed agreement detec-
tion width
0.0 to
20.0
0.1 Hz 2.0 No
L4-05 049D 04 9D Operation when frequency
reference is lost
0 or 110No
L4-06 04C2 04 C2 Frequency reference for
loss of frequency reference
0.0 to
100.0
0.1% 80.0 No
L5-01 049E 04 9E Number of auto restart
attempts
0 to 10 1 0 No
L5-02 049F 04 9F Auto restart operation
selection
0 or 110No
L6-01 04A1 04 A1 Torque detection selection 1 0 to 8 1 0 No
L6-02 04A2 04 A2 Torque detection level 1 0 to 300 1% 150 No
L6-03 04A3 04 A3 Torque detection time 1 0.0 to
10.0
0.1 s 0.1 No
Param-
eter
Register
No.
(Hex)
Class 64 (Hex) Name Setting
range
Setting
unit
Default
setting
Changes
during
opera-
tion
In-
stance
At-
tribute