Setting up Compax3
C3I12T11
236
192-120113 N08 C3I12T11 - December 2010
Flow chart controller optimization of a direct drive
“Controller optimization direct
drive”
Is it a PowerRod?
Status controller with disturbance torque
-“Observer time constant” (Obj. 2120.1) >=125µs
(the higher the value, the slower the observer)
- “Activate disturbance value” (Obj. 2120.7)=1
yes
no
Default settings for PowerRod:
1.) “following error filter” (Obj. 2200.24) = 1470µs
2.) “following error dead zone” (Obj. 2200.20) = 0.025 mm
3.) “Friction feedforward” (Obj. 2200.21) = 0 mA
Vary the default settings if needs be.
See chapters:
-“Control measures for
drives iinvolving friction”
Select speed jerk response in the setup window /
tab “parameter), select the size of the jerk and
define jerk.
Respect the setpoint speed and the actual speed
Smooth, stable behavior?
1.) “Observer time constant” (Obj. 2120.1) and Vary filter of
observed disturbance (Obj. 2120.5) increase “stiffness” (Obj.
2100.2) until the optimum is reached
2.) In systems with high friction, reduce “attenuation” (Obj.
2100.3) and increase “stiffness” (Obj. 2100.2) until the
optimum is reached.
3.) In the event of optimization to speed constancy,
increase “attenuation” (Obj. 2100.3) and reduce “stiffness” as
far as necessary (Obj. 2100.2) until the optimum is reached.
yes
no
Main diagram
Move over the entire positioning range, verify
the settings and correct if necessary.
Store settings with WF!
Stabilize controller with the aid of:
Decrease stiffness (Obj. 2100.2)
or/also reduce observer time constant (Obj. 2120.1)
or/also reduce control signal filter (Obj. 2120.1)
or/also modify attenuation (Obj. 2100.3)
“Controller
optimization
standard”

Table of Contents

Other manuals for Parker Compax3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Compax3 and is the answer not in the manual?

Parker Compax3 Specifications

General IconGeneral
Protection ClassIP20
Control ModesTorque, Speed, Position
Feedback OptionsIncremental encoder, Absolute encoder, Resolver
Communication InterfacesCANopen, EtherCAT, Profinet
Safety FeaturesSTO (Safe Torque Off), SS1 (Safe Stop 1), SOS (Safe Operating Stop)
Input Voltage200-480 VAC
Relative Humidity5% to 85% (non-condensing)
Shock ResistanceAccording to EN 60068-2-27
Operating Temperature0°C to +40°C

Related product manuals