Rexroth EcoDrive Cs Drives Electrical Connections 5-17
DOK-ECODR3-DKC**.3-CS*-PR02-EN-P
The Bb contacts opens:
if control voltage for drive controller is not applied
if 24 volts not present at the emergency stop input when the E-stop
function is activated (depends on parameterization, see Functional
Description).
with an error in the drive (depends on parameterization, see firmware
Functional Description: "Power off on error").
How to use the contact, see page 6-17
WARNING
Damage possible if Bb contact not connected!
The ready to operate contact Bb acknowledges the drive
is ready for mains voltage.
Integrate Bb contact as per "Control Circuits for the
Mains Connection".
The evaluation of the Bb contact by a PLC may not
cause any operating delay of more than 10 ms.
Switching states
Bb: