Supplemental Drive Information A-7
PowerFlex® 700L Liquid-Cooled Drive User Manual
Publication 20L-UM001D-EN-P
Table A.F 400 Volt AC Input Protection Devices
Table A.G 480 Volt AC Input Protection Devices
Table A.H 540 Volt DC Input Fusing
Table A.I 650 Volt DC Input Fusing
Drive
Catalog
Number
Frame
HP (kW) Rating
Input
Rating
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
ND HD Amps Min.
(1)
Max.
(2)
Min. Max. Max.
(4)
Max.
20LC360 2 268 (200) 360 500 750 500 900 900 600
200 (150) 264 400 650 450 900 900 400
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of
motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are
maximum
Drive
Catalog
Number
Frame
HP (kW) Rating
Input
Rating
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
ND HD Amps Min.
(1)
Max.
(2)
Min. Max. Max.
(4)
Max.
20LD360 2 300 (224) 360 500 750 500 900 900 600
235 (175) 264 400 650 450 900 900 400
(1)
Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2)
Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of
motor FLA. Ratings shown are maximum.
(3)
Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum
(4)
Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5)
Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor FLA. Ratings shown are
maximum
Drive
Catalog
Number
Frame
HP (kW) Rating
DC Input
Rating Bussmann Fuse
ND HD Amps Amps Catalog No.
20LC650 3A 500 (370) 365 (270) 1250
(1)
(1)
Only the Dual Inverter for PowerFlex 700L Frame 3A is available as a DC input inverter.
2000 170M6621
(2)
(2)
Two 1000A Bussmann 170M6614 fuses per phase can also be used.
20LC1K2 3B 960 (715) 700 (525) 1250 2000 170M6621
(2)
Drive
Catalog
Number
Frame
HP (kW) Rating
DC Input
Rating Bussmann Fuse
ND HD Amps Amps Catalog No.
20LD650 3A 600 (445) 440 (325) 1250
(1)
(1)
Only the Dual Inverter for PowerFlex 700L Frame 3A is available as a DC input inverter.
2000 170M6621
(2)
(2)
Two 1000A Bussmann 170M6614 fuses per phase can also be used.
20LD1K2 3B 1150 (860) 845 (630) 1250 2000 170M6621
(2)

Table of Contents

Questions and Answers: