Reference Manual
00809-0100-4026, Rev FA
July 2009
Rosemount 5400 Series
7-30
The transmitter displays
“measurement error” and
activates Measurement Alarm
when the product level is close
to the antenna.
May be caused by:
Product level within the Hold Off
region, i.e. outside the approved
measuring range
Action:
Avoid filling the tank to levels very
close to the antenna
Move the transmitter to increase the
distance between maximum product
level and antenna, if possible
Activate the Full Tank Handling
function if measurements up to the
antenna are required, see “Full Tank
Handling” on page C-5 and C-10
The measured level is unstable. May be caused by:
An empty tank with the Amplitude
Threshold too low
Product surface is close to a
registered False Echo
Action:
Create a new Amplitude Threshold
Curve, see “Echo Tuning” on
page 5-10