Commissioning with Terminal PR 5610 Installation Manual
142 Sartorius
• Leave sub-menu 'Test Input/Output'
E Exit
⇒ After leaving this mask (E), return is to sub-menu 'Service'. Only then all outputs set during testing are reset
and the output commands of the PLC programs are retransmitted to the process.
5.7.3.1 PR 1713/04 serial I/O module testing
At the hardware test level, PR 1713/04 serial interface cards can be tested, provided that the following jumpers
are fitted in the terminal blocks:
Terminal block B RS 232 B1 B2 B3 B4 B5 B6 B7 B8
upper row DCD RXD TXD DTR Sign.
GND
RTS CTS RI
DIP switch
settings
S101:
Terminal block A RS485/ 422 A1 A2 A3 A4 A5 A6 A7 A8
bottom row Switch ON
acc. to table
Sign.
GND
TxB TxA RxB RxA nc nc nc
The interfaces are given logic names in the order of allocation found in the slots. In this example, the only card
is always detected as TTY1 and TTY2, whereby TTY1 is the RS 485 and TTY2 is the RS 232 interface.
Output in case of success:
PR1713 Rel. 03.12 20.05.2004 09:05
Test PR1713/04 Slot-Number 1 Mo 06.May 2002 09:31:51
RS485:
Send with RTS ON : passed
Send with RTS OFF: passed (nodata)
Send with RTS ON : passed
RS232:
TxD-RxD : passed
RTS-CTS : passed
DTR-DCD/RI : passed
Output in case of error (e.g.):
PR1713 Rel. 03.12 20.05.2004 09:05
Test PR1713/04 Slot-Number 1 Mo 06.May 2002 09:31:51
RS485:
Send with RTS ON : failed (nodata)
Send with RTS OFF: passed (nodata)
Send with RTS ON : failed (nodata)
RS232:
TxD-RxD : failed (nodata)
RTS-CTS : pattern failed
DTR-DCD/RI : pattern failed