EasyManua.ls Logo

Schweitzer Engineering SEL-351P - Page 228

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-6 Loss-of-Potential, Load Encroachment, and Directional Element Logic Date Code 990430
SEL-351P Manual Técnico
If a fault occurs, the apparent positive-sequence impedance moves outside the ZLOUT area (and
stays outside the ZLIN area, too), resulting in :
ZLOAD = ZLOUT + ZLIN = logical 0 + logical 0 = logical 0
Figure SECTION 4: .3: Migration of Apparent Positive-Sequence Impedance for a
Fault Condition
Refer to Figure 3.14 in Section 3: Overcurrent, Voltage, Synchronism Check, and Frequency
Elements. To prevent phase time-overcurrent element 51P1T from operating for high load
conditions, make the following SEL
OGIC
®
Control Equation torque control setting:
51P1TC = !ZLOAD*!LOP + 50P6 (= NOT[ZLOAD]*NOT[LOP] + 50P6)
As shown in
Figure SECTION 4: .2, load-encroachment logic is a positive-sequence calculation.
During LOP conditions (loss-of-potential; see
Figure SECTION 4: .1), positive-sequence voltage
(V
1
) can be substantially depressed in magnitude or changed in angle. This change in V
1
can
possibly cause ZLOAD to deassert (= logical 0), erroneously indicating that a “fault condition”
exists. Thus, !ZLOAD should be supervised by !LOP in a torque control setting. This also
effectively happens in the directional element in
Figure SECTION 4: .18, where ZLOAD and
LOP are part of the logic.
In the above setting example, phase instantaneous overcurrent element 50P6 is set above any
maximum load current level - if 50P6 picks up, there is assuredly a fault. For faults below the
pickup level of 50P6, but above the pickup of phase time-overcurrent element 51PT, the

Table of Contents