EasyManua.ls Logo

Schweitzer Engineering SEL-351P - Use a Remote Bit Instead to Enable;Disable the Reclosing Relay

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 990215 Inputs, Outputs, Timers, and Other Control Logic 7-15
SEL-351P Manual Técnico
This would then appear to enable the “reset” input (setting RST1), the next processing interval.
But the “rising edge” condition occurred in the preceding processing interval, causing /IN104 to
then deassert to logical 0. So, since /IN104 is now at logical 0, setting RST1 does not assert,
even though input IN104 remains asserted for at least a few cycles by the SCADA contact.
If the SCADA contact deasserts and then asserts again (new rising edge – see Pulse 2 in
Figure SECTION 7: .14), the “reset” input (setting RST1) asserts and latch bit LT1 deasserts
back to logical 0 again. Thus, each individual assertion of input IN104 (Pulse 1, Pulse 2, Pulse 3,
and Pulse 4 in
Figure SECTION 7: .14) changes the state of latch control switch just once.
Note: Refer to preceding subsection Optoisolated Inputs and
Figure SECTION 7: .1. Relay
Word bit IN104 shows the state of optoisolated input IN104 after
the input
pickup/dropout debounce timer IN104D. Thus, when using Relay Word bit IN104 in
Figure SECTION 7: .11 and Figure SECTION 7: .12 and associated SEL
OGIC
Control
Equations, keep in mind any time delay produced by the input pickup/dropout
debounce timer IN104D.
Figure SECTION 7: .14: Latch Control Switch Operation Time Line
Use a Remote Bit Instead to Enable/Disable the Reclosing Relay
Use a remote bit to enable/disable the reclosing relay, instead of an optoisolated input. For
example, substitute remote bit RB1 for optoisolated input IN104 in the settings accompanying
Figure SECTION 7: .13:

Table of Contents