EasyManua.ls Logo

Schweitzer Engineering SEL-351P - Use Existing SEL-321 Relay DCUB Application Guide for the SEL-351 P Recloser Control; External Inputs; LOG1, LOG2 - Loss-Of-Guard Signal(S); PT1, PT2 - Received Permissive Trip Signal(S)

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 990215 Trip and Target Logic 5-19
SEL-351P Manual Técnico
DCUB2 directional comparison unblocking scheme for three-terminal line
(communications from two
remote terminals)
The DCUB logic in
Figure SECTION 5: .10 takes in the loss-of-guard and permissive trip
outputs from the communication receivers (see
Figure SECTION 5: .12 and Figure SECTION 5:
.13) and makes permissive (PTRX1/PTRX2) and unblocking block (UBB1/UBB2) logic output
decisions.
DCUB schemes are typically implemented with FSK (frequency shift carrier) or analog
microwave as the communications medium.
Use Existing SEL-321 Relay DCUB Application Guide for the SEL-351P Recloser Control
Use the existing SEL-321 Relay DCUB application guide (AG96-19) to help set up the SEL-
351P in a DCUB scheme (see preceding subsection Communications-Assisted Trip Logic -
General Overview for more setting comparison information on the SEL-321/SEL-351Ps).
External Inputs
See Optoisolated Inputs in Section 7: Inputs, Outputs, Timers, and Other Control Logic for
more information on optoisolated inputs.
PT1, PT2 – Received Permissive Trip Signal(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), a permissive trip signal is
received from one
remote terminal. One optoisolated input on the SEL-351P (e.g., input IN104)
is driven by a communications equipment receiver output (see
Figure SECTION 5: .12). Make
SEL
OGIC
Control Equation setting PT1:
PT1 = IN104 (two-terminal line application)
In three-terminal line DCUB applications (setting ECOMM = DCUB2), permissive trip signals
are received from two
remote terminals. Two optoisolated inputs on the SEL-351P (e.g., inputs
IN104 and IN106) are driven by communications equipment receiver outputs (see
Figure
SECTION 5: .13). Make SEL
OGIC
Control Equation settings PT1 and PT2 as follows:
PT1 = IN104 (three-terminal line application)
PT2 = IN106
SEL
OGIC
Control Equation settings PT1 and PT2 are routed into the DCUB logic in Figure
SECTION 5: .10 for “unblocking block” and “permissive trip receive” logic decisions.
As explained in the preceding POTT subsection, the SEL
OGIC
Control Equation settings PT1 and
PT2 in
Figure SECTION 5: .5 are routed in various combinations to control Relay Word bit PT,
depending on enable setting ECOMM = DCUB1 or DCUB2. Relay Word bit PT is then an input
into the POTT logic in
Figure SECTION 5: .6 (for echo keying).
LOG1, LOG2 – Loss-of-Guard Signal(s)
In two-terminal line DCUB applications (setting ECOMM = DCUB1), a loss-of-guard signal is
received from one
remote terminal. One optoisolated input on the SEL-351P (e.g., input IN105)

Table of Contents