EasyManua.ls Logo

Schweitzer Engineering SEL-351P - 50 P32 P - Phase Directional Element Three-Phase Current Pickup; Z2 F - Forward Directional Z2 Threshold; Z2 F and Z2 R Set Automatically; Z2 R - Reverse Directional Z2 Threshold

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-30 Loss-of-Potential, Load Encroachment, and Directional Element Logic Date Code 990430
SEL-351P Manual Técnico
If setting:
ORDER = OFF
then the two directional elements (Q and V) are inoperable. Note in
Figure SECTION 4: .14 and
Figure SECTION 4: .15 that setting ORDER = OFF effectively makes the neutral ground and
residual ground overcurrent elements nondirectional (the directional control outputs of
Figure SECTION 4: .14 and Figure SECTION 4: .15 are continuously asserted to logical 1).
50P32P – Phase Directional Element Three-Phase Current Pickup
Setting Range:
0.1 - 2.00 A secondary (1 A nominal phase current inputs, IA, IB, IC)
The 50P32P setting is set to pick up for all three-phase faults that need to be covered by the
phase overcurrent elements. It supervises the positive-sequence voltage-polarized directional
elements F32P and R32P (see
Figure SECTION 4: .18).
If the load-encroachment logic is enabled (enable setting ELOAD = Y), then setting 50P32P is
not made or displayed, but is fixed internally at:
0.1 A secondary (1 A nominal phase current inputs, IA, IB, IC)
Z2F – Forward Directional Z2 Threshold
Z2R – Reverse Directional Z2 Threshold
Setting Range:
-320.00 to 320.00 Ω secondary (1 A nominal phase current inputs, IA, IB, IC)
Z2F and Z2R are used to calculate the Forward and Reverse Thresholds, respectively, for the
negative-sequence voltage-polarized directional elements (see
Figure SECTION 4: .9 and
Figure SECTION 4: .17).
Z2F and Z2R Set Automatically
If enable setting E32 = AUTO, settings Z2F and Z2R (negative-sequence impedance values) are
calculated automatically, using the positive-sequence line impedance magnitude setting Z1MAG
as follows:
Z2F = Z1MAG/2 (Ω secondary)
Z2R = Z1MAG/2 + 0.5 (Ω secondary)
If enable setting E32 = Y, settings Z2F and Z2R (negative-sequence impedance values) are
calculated by the user and entered by the user, but setting Z2R must be at least 0.5 Ω secondary
greater in value than setting Z2F.

Table of Contents