Specifications
78 SEL-351P Quick-Start Installation and User's Guide (Portuguese)
Metering Accuracy
Accuracies are specified at 20°C and at nominal system frequency unless noted otherwise.
Voltages V
A
, V
B
, V
C
, V
S
, 3•V
0
, V
1
, V
2
±0.2% (33.5 - 150 V)
Currents I
A
, I
B
, I
C
±0.3 mA and ±0.1% (0.1 - 2 A) (1 A nominal)
Temperature coefficient:
[(0.0002%)/(°C)
2
] * (___°C - 20°C)
2
(see example below)
Currents I
N
, I
1
, 3•I
0
, 3•I
2
±0.01 A and ±3% (0.1 - 20 A) (1 A nominal)
±1 mA and ±5% (0.01 - 1.5 A) (0.05 A nominal
channel IN current input)
Phase Angle Accuracy
±1.0°
Metering accuracy calculation example for currents I
A
, I
B
, and I
C
due to preceding stated temperature
coefficient:
For temperature of 40°C, the additional
error for currents I
A
, I
B
, and I
C
is:
[(0.0002%)/(°C)
2
] * (40°C - 20°C)
2
= 0.08%