EasyManua.ls Logo

Schweitzer Engineering SEL-351P - 50 GFP - Forward Directional Residual Ground Current Pickup; 50 GFP and 50 GRP Set Automatically; 50 GRP - Reverse Directional Residual Ground Current Pickup; A0 - Positive-Sequence Current Restraint Factor, I

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 990430 Loss-of-Potential, Load Encroachment, and Directional Element Logic 4-33
SEL-351P Manual Técnico
50GFP – Forward Directional Residual Ground Current Pickup
50GRP – Reverse Directional Residual Ground Current Pickup
Setting Range:
0.05 - 1.00 A secondary (1 A nominal phase current inputs, IA, IB, IC)
If preceding setting ORDER does not contain V (zero-sequence voltage-polarized directional
element is not enabled), then settings 50GFP and 50GRP are not made or displayed.
The 50GFP setting (3I
0
current value) is the pickup for the forward fault detector 50GF of the
zero-sequence voltage-polarized, residual-current directional element (see
Figure SECTION 4:
.6). Ideally, the setting is above normal load unbalance and below the lowest expected zero-
sequence current magnitude for unbalanced forward faults.
The 50GRP setting (3I
0
current value) is the pickup for the reverse fault detector 50GR of the
zero-sequence voltage-polarized, residual-current directional element (see
Figure SECTION 4:
.6). Ideally, the setting is above normal load unbalance and below the lowest expected zero-
sequence current magnitude for unbalanced reverse faults.
The 50GFP/10 setting (I
N
current value) is the pickup for the forward fault detector 50NF of the
zero-sequence voltage-polarized, neutral-current directional element (see
Figure SECTION 4:
.7). This setting is always automatic and used for SEF applications.
The 50GRP/10 setting (I
N
current value) is the pickup for the reverse fault detector 50NR of the
zero-sequence voltage-polarized, neutral-current directional element (see
Figure SECTION 4:
.7). This setting is always automatic and used for SEF applications.
50GFP and 50GRP Set Automatically
If enable setting E32 = AUTO, settings 50GFP and 50GRP are set automatically at:
50GFP = 0.10 A secondary (1 A nominal phase current inputs, IA, IB, IC)
50GRP = 0.05 A secondary (1 A nominal phase current inputs, IA, IB, IC)
a0 – Positive-Sequence Current Restraint Factor, I
0
/I
1
Setting Range:
0.02 - 0.50 (unitless)
If preceding setting ORDER does not contain V (zero-sequence voltage-polarized directional
element is not enabled), then setting a0 is not made or displayed.
Refer to
Figure SECTION 4: .6.
The a0 factor increases the security of the zero-sequence voltage-polarized directional element.
It keeps the element from operating for zero-sequence current (system unbalance), which
circulates due to line asymmetries, CT saturation during three-phase faults, etc.
a0 Set Automatically

Table of Contents