Date Code 990215 Serial Port Communications and Commands 10-15
SEL-351P Manual Técnico
B EDITH
2 TAIL
Access Level Attempt (password required)
Assume the following conditions: Password jumper = OFF (not in place), Access Level = 0.
At the Access Level 0 prompt, enter the ACC command:
=ACC <ENTER>
Because the Password jumper is not in place, the control asks for the Access Level 1 password to
be entered:
Password: ? @@@@@@
The control is shipped with the default Access Level 1 password “OTTER”. Enter the default
password:
Password: ? OTTER <ENTER>
The control responds:
RECLOSER R1 Date: 03/05/97 Time: 08:31:10.361
FEEDER 2101
Level 1
=>
The “=>” prompt indicates the control is now in Access Level 1.
If the entered password is incorrect, the control asks for the password again (Password: ?). The
control will ask up to three times. If the requested password is incorrectly entered three times,
the control pulses the ALARM contact for one second and remains at Access Level 0 (“=”
prompt).
Access Level Attempt (password not required)
Assume the following conditions: Password jumper = ON (in place), Access Level = 0.
At the Access Level 0 prompt, enter the ACC command:
=ACC <ENTER>