Date Code 990430 SEL-351P Command Summary Page 1 of 3
SEL-351P Manual Técnico
SEL-351P RECLOSER CONTROL COMMAND SUMMARY
Access
Level 0
Command
From Access level 0, you can go to Access Level 1 or to Access Level E (EZ).
The Access Level 0 screen prompt is: =
ACC Enter Access Level 1. If the main board password jumper is not in place, the control prompts you
for the Access Level 1 password to enter Access Level 1.
EZA Enter Access Level E (EZ). If the main board password jumper is not in place, the control prompts
you for the Access Level E password to enter Access Level E.
Access
Level 1
Command
The Access Level 1 commands primarily allow you to look at information (e.g., settings,
metering), not change it. The Access Level 1 screen prompt is: =>
2AC Enter Access Level 2. If the main board password jumper is not in place, the control prompts you
for the Access Level 2 password to enter Access Level 2.
BAC Enter Access Level B (Breaker) . If the main board password jumper is not in place, the control
prompts you for the Access Level B password.
BRE A Display breaker/recloser monitor data (trips, interrupted current, % contact wear).
COM p L Show a long format communications summary report for all events on M
IRRORED BITS channel
p.
COM p n Show a communications summary for latest n event on M
IRRORED BITS channel p.
COM p m n Show a communications summary report for events n through m on M
IRRORED BITS channel p.
COM p d1 Show a communications summary report for events occurring on date d1 on M
IRRORED BITS
channel p.
COM p n Show a communications summary for events occurring between dates d1 and d2 on M
IRRORED
BITS channel p. Entry of dates is dependent on the Date Format setting DATE_F (= MDY or
YMD)
DAT Show date.
DAT m/d/y Enter date in this manner if Date Format setting DATE_F = MDY.
DAT y/m/d Enter date in this manner if Date Format setting DATE_F = YMD.
EVE n Show event report number n with 1/4-cycle resolution.
EVE L n Show event report number n with 1/16-cycle resolution.
EVE R n Show raw event report number n with 1/16-cycle resolution.
EVE C n Show compressed event report number n for use with SEL-5601 Analytic Assistant.
EVE XX f Append parameter f to any of the above EVE commands, where f is A or D. Use A to show only
the Analog portion of the event report, Use D to show only the digital protection and control
portion of the event report
EZA Enter Access Level E (EZ). If the main board password jumper is not in place, the control prompts
you for the Access Level E password to enter Access Level E.
GRO Display active settings group number.
HIS n Show brief summary of the n latest event reports.
HIS C Clear the brief summary and corresponding event reports.
IRI Force synchronization of internal control clock to IRIG-B time-code input.
LDP n Show the latest n rows in the Load Profile report.