6-12 Close and Reclose Logic Date Code 990215
SEL-351P Manual Técnico
Reclosing Relay States and General Operation
Figure SECTION 6: .5 explains in general the different states of the reclosing relay and its
operation.
Figure SECTION 6: .5: Reclosing Relay States and General Operation
Table SECTION 6: .1: Relay Word Bit and Front-Panel Correspondence to Reclosing
Relay States
Reclosing Relay State
Corresponding
Relay Word Bit
Corresponding
Front-Panel LED
Reset 79RS RS
Reclose Cycle 79CY CY
Lockout 79LO LO
The reclosing relay is in one (and only one) of these states (listed in Table SECTION 6: .1) at
any time. When in a given state, the corresponding Relay Word bit asserts to logical 1, and the
LED illuminates. Automatic reclosing only takes place when the relay is in the Reclose Cycle
State.