EasyManua.ls Logo

Schweitzer Engineering SEL-351P - BTX - Block Trip Extension; Installation Variations

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Date Code 990215 Trip and Target Logic 5-27
SEL-351P Manual Técnico
BTX – Block Trip Extension
The received block trip input (e.g., BT = IN104) is routed through a dropout timer (BTXD) in the
DCB logic in
Figure SECTION 5: .14. The timer output (BTX) is routed to the trip logic in
Figure SECTION 5: .1.
Figure SECTION 5: .14: DCB Logic
Installation Variations
Figure SECTION 5: .16 shows output contacts OUT104, OUT105, OUT106, and OUT107
connected to separate communications equipment for the two remote terminals. Both output
contact pairs are programmed the same (OUT105 = DSTRT + NSTRT and
OUT107 = DSTRT + NSTRT; OUT106 = STOP and OUT104 = STOP).
Depending on the installation, perhaps one output contact (e.g., OUT105 = DSTRT + NSTRT)
can be connected in parallel to both START inputs on the communications equipment in
Figure
SECTION 5: .16. Then output contact OUT107 can be used for another function.

Table of Contents