Date Code 990215 Factory-Set Logic 1-43
SEL-351P Manual Técnico
FECHAR
ABRIR
DWG: MP351P02
SEF
HABILITADO
PROTEÇÃO
BLOQUEADA
DESPERTAR
RELIGADOR
FECHADO
RELIGADOR
ABERTO
LED
Operator
Control
Pushbutton
Relay
Word
Bit Output
SEL
OGIC
Factory
Setting
Detailed
Operator
Control
Pushbutton
Output
Correspondin
LED Operatio
and Logic
Application
PB6 LED6 = LT5
PB7 LED7 = 0
(always extinguished from
factory)
PB8 LED8 = 52A
PB9 LED9 = !52A
= NOT (52A)
Similar to
Figure 1.33 Figure 1.41
Similar to
Figure 1.33 Figure 1.42
Figure 1.35 Figure 1.20
Figure 1.36 Figure 1.19
Time Delays are available for the ABRIR and FECHAR operator control pushbuttons (global settings
PB8D and PB9D, respectively; settable up to 3600 cycles). These time delay settings are set to
zero from the factory (no time delay; PB8D = 0, PB9D = 0).
Figure SECTION 1: .32: Operator Controls – SEF HABILITADO through ABRIR
Detailed Operator Control Pushbutton Output
Figure SECTION 1: .31 and Figure SECTION 1: .32 list corresponding figures that detail
operator control pushbutton output and corresponding LED operation and logic operation. Note
that the pushbutton output (e.g., Relay Word bit PB1
for the TERRA HABILITADO operator
control pushbutton) corresponds number-wise to the LED setting (e.g., SEL
OGIC
setting LED1
for the TERRA HABILITADO LED).
TERRA HABILITADO Operator Control Pushbutton Output
Figure SECTION 1: .33 describes the TERRA HABILITADO operator control pushbutton
output. Every time the TERRA HABILITADO operator control pushbutton is pressed
momentarily, Relay Word bit PB1 asserts to logical 1 immediately for one processing interval.
The corresponding TERRA HABILITADO LED (controlled by SEL
OGIC
setting LED1) is
independent of the TERRA HABILITADO operator control pushbutton.