EasyManua.ls Logo

Schweitzer Engineering SEL-351P - Input Debounce Timers

Default Icon
674 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7-2 Inputs, Outputs, Timers, and Other Control Logic Date Code 990215
SEL-351P Manual Técnico
Figure SECTION 7: .1: Example Operation of Optoisolated Inputs IN101 Through
IN106
Input Debounce Timers
See
Figure SECTION 7: .1.
Each input has settable pickup/dropout timers (IN101D through IN106D) for input
energization/deenergization debounce. Note that a given time setting (e.g., IN101D = 0.50) is
applied to both the pickup and dropout time for the corresponding input.
Time settings IN101D through IN106D are settable from 0.00 to 1.00 cycles. The SEL-351P
takes the entered time setting and internally runs the timer at the nearest 1/16-cycle. For
example, if setting IN5D = 0.80, internally the timer runs at the nearest 1/16-cycle: 13/16-cycles
(13/16 = 0.8125).
For most applications
, the input pickup/dropout debounce timers should be set in 1/4-cycle
increments. For example, in the factory default settings
, all the optoisolated input
pickup/dropout debounce timers are set at 1/2-cycle (e.g., IN104D = 0.50). See SHO Command
(Show/View Settings) in Section 10: Serial Port Communications and Commands for a list of
the factory default settings.
Only a few applications
(e.g., communications-assisted tripping schemes) might require input
pickup/dropout debounce timers set less than 1/4-cycle [e.g., if setting IN105D = 0.13, internally
the timer runs at the nearest 1/16-cycle: 2/16-cycles (2/16 = 0.1250)].
The relay processing interval is 1/4-cycle, so Relay Word bits IN101 through IN106 are updated
every 1/4-cycle. The optoisolated input status may have made it through the pickup/dropout
debounce timer (for settings less than 1/4-cycle) because these timers run each 1/16-cycle, but
Relay Word bits IN101 through IN106 are updated every 1/4-cycle.

Table of Contents