10-26 Serial Port Communications and Commands Date Code 990215
SEL-351P Manual Técnico
The SEL-351P sets the port access level to 0 and responds:
RECLOSER R1 Date: 03/05/97 Time: 08:55:33.986
FEEDER 2101
=
The “=” prompt indicates the control is back in Access Level 0.
The QUI command terminates the SEL Distributed Port Switch Protocol (LMD) connection if it
is established [see Appendix C: SEL Distributed Port Switch Protocol for details on SEL
Distributed Port Switch Protocol (LMD)].
SER Command (Sequential Events Recorder Report)
Use the SER command to view the Sequential Events Recorder report. For more information on
SER reports, see Section 12: Standard Event Reports and SER.
SHO Command (Show/View Settings)
Use the SHO command to view “regular” settings, EZ recloser control settings, global settings,
SEL
OGIC
Control Equations settings, serial port settings, sequential events recorder (SER)
settings, and text label settings. Below are the SHO command options.
SHO n Show “regular” settings for settings group n. n specifies
the settings group (1, 2, 3, 4, 5, or 6); n defaults to the
active settings group if not listed.
SHO EZ n Show EZ recloser control settings for settings group n. n
specifies the settings group (1, 2, 3, 4, 5, or 6); n defaults
to the active settings group if not listed.
SHO FZ
Show EZ global settings.
SHO G
Show global settings.
SHO L n
Show SEL
OGIC
Control Equation settings for settings
group n. n specifies the settings group (1, 2, 3, 4, 5, or 6);
n defaults to the active settings group if not listed.
SHO P n Show serial port settings. n specifies the port (1, 2, 3, or
F); n defaults to the active port if not listed.
SHO R
Show sequential events recorder (SER) settings.
SHO T
Show text label settings for the front panel display points.
Also, see Table 9.1 in Section 9: Setting the SEL-351P Recloser Control for settings sheet
references.