10-42 Serial Port Communications and Commands Date Code 990430
SEL-351P Manual Técnico
Continued from Previous Page
Cntrl Trips= 16
IA= 40.7 IB= 41.4 IC= 53.8 kA
Ext Trips= 3
IA= 0.8 IB= 0.9 IC= 1.1 kA
Percent wear: A= 8 B= 7 C= 10
A-phase Trips= 14
B-phase Trips= 9
C-phase Trips= 10
EF/G Trips= 12
SEF Trips= 0
LAST RESET 12/27/98 15:32:59
==>
Use the BRE R command to reset the breaker/recloser contact wear monitor:
==>BRE R <ENTER>
RECLOSER R1 Date: 02/03/99 Time: 08:44:20.802
FEEDER 2101
Ctrl Trips= 16
IA= 40.7 IB= 41.4 IC= 53.8 kA
Ext Trips= 3
IA= 0.8 IB= 0.9 IC= 1.1 kA
Percent wear: A= 8 B= 7 C= 10
A-phase Trips= 14
B-phase Trips= 9
C-phase Trips= 10
EF/G Trips= 12
SEF Trips= 0
LAST RESET 12/27/98 15:32:59
Reset Trip Counters and Accumulated Currents/Wear
Are you sure (Y/N) ? Y <ENTER>
RECLOSER R1 Date: 02/03/99 Time: 08:44:33.920
FEEDER 2101
Cntrl Trips= 0
IA= 0.0 IB= 0.0 IC= 0.0 kA
Ext Trips= 0
IA= 0.0 IB= 0.0 IC= 0.0 kA
Percent wear: A= 0 B= 0 C= 0
Continued on Next Page
Continued from Previous Page
A-phase Trips= 0
B-phase Trips= 0
C-phase Trips= 0
EF/G Trips= 0
SEF Trips= 0