Date Code 990430 Configuration, Fast Meter, and Fast Operate Commands D-3
SEL-351P Manual Técnico
FF Scale factor type
0000 Scale factor offset in Fast Meter message
494200000000 Analog channel name (IB)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
494300000000 Analog channel name (IC)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
494E00000000 Analog channel name (IN)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
564100000000 Analog channel name (VA)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
564200000000 Analog channel name (VB)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
564300000000 Analog channel name (VC)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
565300000000 Analog channel name (VS)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
465245510000 Analog channel name (FREQ)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
564241540000 Analog channel name (VBAT)
01 Analog channel type
FF Scale factor type
0000 Scale factor offset in Fast Meter message
00 Line Configuration (0-ABC, 1-ACB)
00 Standard Power Calculations
FFFF No Deskew angle
FFFF No Rs compensation (-1)
FFFF No Xs compensation (-1)
00 IA channel index
01 IB channel index
02 IC channel index
04 VA channel index