13
Parameter setting
Parameter descriptions
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
214
P560 Current limit Ex-e motor
Setting range: On/Off
• Setting "On:" Current limitation for Ex‑e motors is active. The current limiting is
already activated during startup for the Ex-e operation selected and approved mo-
tors. The current limit (→2203) can no longer be changed when the protection
function is active.
• Setting "Off": Current limiting for Ex‑e motors is not active.
P561 FrequencyA
Setting range: 0–5–60Hz
Value for minimum operating frequency f
A
. The device is operated independently of
the current amount for 60s at the operating frequencyf
A
. After this time elapses, the
device switches off and displays the error message "A1.F110" ("Ex e protection") .
P562 Current limitationA
Setting range: 0–50–150%
Current limitation that is permitted with operating frequency f
A
. There is a linear gradi-
ent between current limitationA and current limitationB.
P563 FrequencyB
Setting range: 0–10–104Hz
Value for operating frequencyf
B
.
P564 Current limitB
Setting range: 0–80–200%
Current limitation that is permitted with operating frequencyf
B
. There is a linear gradi-
ent between current limitB and current limitC.
P565 FrequencyC
Setting range: 0–25–104Hz
Value for operating frequencyf
C
.
P566 Current limitC
Setting range: 0–100–200%
Current limit that is permitted between operating frequency f
C
and rated motor fre-
quency. The rated motor frequency is 50Hz for star connection and 87Hz for delta
connection. After startup with an Ex-e motor, the current limitC is approximately equal
to the rated motor current I
N
.
16998413/EN – 12/2016