13
Parameter setting
Parameter descriptions
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
203
P303/P313 Current limit 1/2
1
2
AUTO
Setting range: 0 – 150% of the nominal motor data I
N
The factory setting for the current limitation is set to 150% I
N
of the matching motor.
The internal current limitation is based on the apparent current. In the operating
modes "V/f" and "VFC" without speed control, the current limit is automatically re-
duced in field weakening mode above the frequency of 1.15 × f
base
. This implements
stall protection for the connected motor. The current limit effective in the field weaken-
ing range is calculated using the following formula:
Current limit
f
f
actual
= × ×( , )115
setting value P303/P313
base
18327565835
f
base
Base frequency
f
actual
Current rotational frequency
P304 Torque limit
1
2
AUTO
The parameter is only effective in "CFC and "Servo" operating modes.
Setting range: 0–150%
Limits the maximum torque of the motor. The entry acts on the setpoint of the motor
torque (k
T
×I
N
(device)). In order to ensure secure triggering of the speed monitoring,
the parameter value must always be less than or equal to the current limit (→2203).
P32./P33. Motor adjustment1/2
P320/P330 Automatic adjustment1/2
1
2
The parameter is only effective in "VFC and "V/f" operating modes. The function is
only useful for single motor operation.
Setting range: ON/OFF
When the parameter is activated, the device automatically adjusts the parameter
P322/P332 IxR adjustment 1/2 with every enable and saves the value. The device
thereby determines a basic setting that is adequate for a great number of drive applic-
ations. The connected motor is calibrated in the last 20 ms of the premagnetization
phase, except if:
the parameter is deactivated
the operating modes "VFC&Group" or "VFC&flying start function" are set
the pre-magnetization time (→2205) has been reduced by more than 30ms in
relation to the proposed value.
in the operating mode "VFC n-control," the parameter P730/P733 brake function
1/2 (→2219) is deactivated.
In such cases, the set IxR value is used for calculating the winding resistance.
P321/P331 Boost1/2
1
2
Setting range: 0–100%
16998413/EN – 12/2016