5
Installation notes
Connection to the Ethernet network
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
34
Status and error messages
The status display on the device cover shows the current device status. In case of re-
peated malfunctions, contact the SEW‑EURODRIVE Service.
If several statuses or faults are active at the same time, the status display shows the
status or fault with the highest priority.
The device status display takes priority over the display of the internal "PFA-..." power
section. If the maintenance switch is switched off or a fieldbus fault occurs, no power
section status is displayed.
Display examples
The following examples show how the device usually displays status and fault mes-
sages.
Example 1: "Enable" of power section 1
1820269707
Example 2: "Overtemperature" fault of power section 1
If the display shows "A[Power section number].F", a power section fault occurred. The
display switches between the number of the power section and the fault code.
1806505867
Refer to chapter "List of power section errors" (→ 2 248) for an overview of power
section faults.
Status messages
If you use a parameterizable device, the following status messages are possible.
Code Meaning Possible cause Measure
8.8.8.
S2:
Flashing
green
S3:
Off
Application module not run-
ning/not loaded
Create a configuration with
the Application Configurator
and load it into the device.
A1.0 DC 24V operation, frequency
inverter not ready
A1.1 Controller inhibit active
A1.2 No enable
A1.3 Standstill current
A1.4 Enable
A1.5 n-control
A1.6 M-control